Installation
28 — English
Reflexomat with Basic controller — 20.06.2017 - Rev. C
6.5
Electrical connection
DANGER
Risk of serious injury or death due to electric shock.
If live parts are touched, there is risk of life-threatening injuries.
•
Ensure that the system is voltage-free before installing the device.
•
Ensure that the system is secured and cannot be reactivated by other persons.
•
Ensure that installation work for the electric connection of the device is carried out by an electrician, and in compliance with
electrical engineering regulations.
The following descriptions apply to standard systems and are limited to the necessary user-provided connections.
1. Disconnect the system from the power source and secure it against unintentional reactivation.
2. Remove the cover.
DANGER Risk of serious injury or death due to electric shock. Some parts of the device's circuit board may still carry 230 V
voltage even with the device physically isolated from the power supply. Before you remove the covers, completely isolate the device
controller from the power supply. Verify that the main circuit board is voltage-free.
3. Install a screwed cable gland suitable for the respective cable. M16 or M20, for example.
4. Thread all cables to be connected through the cable gland.
5. Connect all cables as shown in the terminal diagram.
– Note that the fusing for the device connection is to be provided by the user, see chapter 6.5.1 "Terminal diagram" on page 29 .
6. Install the cover.
7. Connect the mains plug to the 230 V power supply.
8. Activate the system.
The electrical connection is completed.