4.2 Fault
Display
TVMS Output Fuse
blown
Fault screens will be shown if either an output fuse is blown, a connected Inverter or
Manager has a fault or if the unit encounters a switching fault.
Fuse Faults
When a fuse fault is detected (ie, a fuse is blown) the output channel will be turned off and
the corresponding icon on the display will be shown in red. Additionally the LED adjacent
to the fuse will illuminate as described in Section 2.5.3 Blown Fuse Indicators on page
17. The fault will clear automatically once the fuse is replaced.
Switching Errors
In the event that a switching error is detected, the relevant output channel will be turned
off and the corresponding icon on the display will be shown in red.
After 60 seconds, the channel will be turned ON again;
• If the error has been fi xed the channel will remain ON.
• If the error is still present the channel will turn OFF again immediately.
While the channel is ON and in switching error mode, RedVision will re-attempt to turn
the load on every 60 seconds. During this time the user may turn the channel OFF
permanently. (Note that the ability to turn the channel OFF only applies to user-controlled
channels - some channels may be automatically switched depending on the confi guration
of the system.)