16
2 INSTALLATION
GUIDE
2.5 Fuses
2.5.1 Fuse Locations
The Distribution Box load output channels are protected by standard blade fuses located
in the fuse panel:
Qty
Part
Type
5
10A Max Loads
Blade
Fuses Not Supplied
5
30 Max Loads
Blade
Fuses Not Supplied
4
Spare Fuse Holders
Blade
Fuses Not Supplied
1
50A Charger Fuse
MIDI
Supplied
1
Spare Fuse Holder
MIDI
Supplied
Additionally a 1 x 80A Battery Fuse and Fuse Holder are supplied.
To protect the Distribution Box from harsh startup currents, inductive type loads (e.g. large
fridges, pumps, motors) should be connected through the 30A Max circuits.
2.5.2 Load Negatives
Wire each load positive (+) and negative (-) to the applicable output channel. Alternatively,
load negatives may be connected at a suitable chassis grounding point.
Risk of damage to the system. Do NOT connect a load negative (-) to the chassis AND to
the applicable negative (-) output channel as this may cause damage to the Distribution
Box under some circumstances. Connect to the applicable negative (-) output channel OR
a suitable chassis grounding point to avoid damage.
50A Charger Fuse
Spare Charger Fuse
Override Switches
10A Max
Circuit Fuses
Spare Fuses
30A Max Circuit Fuses