Datamate 2200 O&M
Page 31
SECTION 7: STARTUP
7.1 Power
NOTE: Access to field wiring and circuit board terminals is not required during
flow meter start-up or zeroing.
After wiring connections have been made (Section 3.5), power can be supplied to the
Datamate 2200 transmitter.
Start-up Mode:
During start-up and initialization, the following start-up indicators can be
observed:
• 4-20mA and pulse outputs go to undefined fallback levels
• The optional LCD on the cover reads for two seconds, “R
ed
S
eal
M
easurement
Coriolis Flow Transmitter”
• The display on the HART
®
Communicator reads “Field device warming up”
• Alarm outputs are active
Operating Mode:
After startup, the optional LCD display will indicate process
measurements.
7.2 Startup with NexLink PC Software
Using Figure 5.6.1, complete wiring connections between the Datamate 2200 transmitter
and an IBM compatible PC with RS485 serial interface.
At the Datamate 2200 using the following MENU TREE enter Comm Ports
From the Main Display press <Enter>, <3. Program>, <1. View Measurements>,
<3. Program>, <3. Configuration>, <6. Outputs>, <5. Comm Ports>
Under Comm Ports select the following: Comm Port:
1-4
, Baud Rate:
9600
,
Parity: None, Data Bits:
8
, Stop Bits:
1
, Protocol:
Modbus
, Modbus Mode:
ASCII
, Unit
ID:
Select any number between 1-247.
NOTE: All Datamate 2200 transmitters in the blind configuration are
pre-programmed from the factory with ID number “247.” Any change to the
Unit ID or protocol, power to the Datamate 2200 is to be recycled for the change
to be acknowledged. The default password for NexLink: User ID: admin
,
Password: admin
To change the Unit ID for a blind unit, within the NexLink PC software in the Configuration
menu select <Outputs> and <Comm Port>.
Within the NexLink PC software, select the Comm Port pull-down menu from the Main
Menu and configure the setting to match the Datamate 2200 transmitter settings. When all
settings match, reboot the Datamate 2200 transmitter.
Within NexLink open up the “Comm Port” menu using the displayed icon, select
View Measurements under the “Process Variables” pull down menu. If the NexLink
is communicating with the Datamate 2200, the displayed measurement values will
correspond to the Datamate 2200 display. If no communication exists, the NexLink PC
software will respond with “Closing Comm Port.” If this occurs, re-check wiring and
communication settings.