background image

LCD INSTALLATION AND OPERATION INSTRUCTIONS

Page 13

f)   After it has been determined that each appliance 

remaining connected to the common venting system 
properly vents when tested as outlined above, return 
doors, windows, exhaust fans, fi replace dampers 
and any other gas-burning appliance to their 
previous condition of use.

 

Une fois qu'il a été d éterminé, selon la métode 
indiquée ci-dessus, que chaque appareil raccordé 
au système d'évacuation est mis à l'air libre de façor 
adéquate. Remettre les portes et les fenêtres, les 
ventilateurs, les registres de cheminées et les 
appareils au gaz à leur position originale.

g)   Any improper operation of the common venting 

system should be corrected so the installation 
conforms with the National Fuel Gas Code, ANSI 
Z223.1/NFPA 54. When resizing any portion of the 
common venting system, the common venting 
system should be resized to approach the minimum 
size as determined using the appropriate tables in 
Appendix F in the National Fuel Gas Code, ANSI 
Z223.1/NFPA 54 and or CAN/CGA-B149 Installation 
Codes.

 

Tout mauvais fonctionnement du systéme d'évacu-
tion commun devrait étré corrigé de façor que 
l'installation soit conforme au National Fue Gas 
Code, ANSI Z223.1/NFPA 54 et (ou) aux codes 
d'installation CAN/CGA-B149. Si la grosseur d'une 
section du système d' évacuation doit étré modifi ée, 
le système devrait étré modifi é pour respecter les 
valeurs minimales des tableaux pertinents de 
l'appendice F du National Fuel Gas Code, ANSI 
Z223.1/ NFPA 54 et (ou) des codes d'installation 
CAN/CGA-B149.

GENERAL PIPING REQUIREMENTS

CAUTION: Improper piping of this boiler/water heater 
will void the manufacturer's warranty and can cause 
boiler failure resulting in fl ooding and extensive 
property damage! Excessive water hardness causing 
scaling in the copper heat exchanger tubes is 

NOT

 

covered under the manufacturer’s warranty. 
Excessive pitting and erosion of the internal surface 
of the copper heat exchanger tubes is 

NOT

 covered 

under the manufacturer’s warranty if the result of 
high water fl ow rates, see Table 7. Return water 
temperatures below 125°F, 

52°C

 will result in heat 

exchanger damage from excessive condensation 
voiding the manufacturer’s warranty, see Primary/
Secondary Piping Figure 11.

NOTE: Shut off valves and unions should be 
installed at the inlet and outlet connections of the 
boiler/water heater to provide for isolation of the unit 
should servicing be necessary.

Table 7 - Temperature Rise Table 

 

Δ

T = 15 °F 

Δ

T = 8.3 °C

 

Model

 Flow 

Rate 

Pres. 

Drop 

Flow Rate  

Pres. Drop

 

Number

 GPM 

Ft 

L/s kPa

 225 

24.6 0.18

 

1.6 0.5

 300 

32.8 0.31

 

2.1 0.9

 400 

43.7 0.70

 

2.8 2.1

 600 

65.6 1.84

 

4.1 5.4

 750 

82.0 3.32

 

5.2 9.8

 

Δ

T = 20 °F 

Δ

T = 11.1 °C

  

Model

 

Flow Rate   Pres. Drop 

Flow Rate    Pres. Drop 

 Number

 

GPM  

Ft  

L/s  

kPa

 300 

24.6 0.18

 

1.6 0.5

 400 

32.8 0.41

 

2.1 1.2

 600 

49.2 1.08

 

3.1 3.2

 750 

61.5 1.95

 

3.9 5.7

 1050 

86.1 5.16

 

5.4 15.2

 1200 

98.4* 8.14

 

6.2 24.0

 1480 

121.4* 7.94

 

7.7 23.4

 

Δ

T = 25 °F 

Δ

T = 13.9 °C

 

 Model

 

Flow Rate   Pres. Drop 

Flow Rate    Pres. Drop 

 Number

 GPM 

Ft 

L/s kPa

 400 

26.2 0.27

 

1.7 0.8

 600 

39.4 0.71

 

2.5 2.1

 750 

49.2 1.29

 

3.1 3.8

 1050 

68.9 3.41

 

4.3 10.1

 1200 

78.7 5.38

 

5.0 15.9

 1480 

97.1 5.25

 

6.1 15.5

 1650 

108.2 7.02

 

6.8 20.7

 

Δ

T = 30 °F 

Δ

T = 16.7 °C

 

Model

 Flow 

Rate 

Pres. 

Drop 

Flow Rate 

Pres. Drop

 Number

 GPM 

Ft 

L/s kPa

 600 

32.8 0.51

 

2.1 1.5

 750 

41.0 0.92

 

2.6 2.7

 1050 

57.4 2.44

 

3.6 7.2

 1200 

65.6 3.84

 

4.1 11.3

 1480 

80.9 3.75

 

5.1 11.0

 1650 

90.2 5.01

 

5.7 14.8

 1970 

107.7 8.75

 

6.8 25.8

 2300 

125.7* 12.45

 

7.9 36.7

 

Δ

T = 35 °F 

Δ

T = 19.4 °C

 

Model

 Flow 

Rate 

Pres. 

Drop 

Flow Rate 

Pres. Drop

 

Number

 GPM 

Ft 

L/s kPa

 600 

28.1 0.38

 

1.8 1.1

 750 

35.1 0.69

 

2.2 2.0

 1050 

49.2 1.83

 

3.1 5.4

 1200 

56.2 2.89

 

3.5 8.5

 1480 

69.3 2.82

 

4.4 8.3

 1650 

77.3 3.77

 

4.9 11.1

 1970 

92.3 6.58

 

5.8 19.4

 2300 

107.8 9.36

 

6.8 27.6

*Flow exceeds recommended maximum use a greater temperature 
rise or consult manufacturer. Cupro-Nickel exchanger should be 
considered.

Содержание LCD Series

Страница 1: ...se gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not...

Страница 2: ...form to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 In Canada the installation must be in accordance with the requirements of CSA B149 1 or 2 Installat...

Страница 3: ...acent construction should a leak occur or during routine maintenance If such a location doesn t exist a suitable drain pan that s adequately drained must be installed under the unit 5 DO NOT place thi...

Страница 4: ...the minimum clearances listed in Table 1 must be maintained between it and any combustible construction When installed in a confined space without the intake air option Figures 1 2 3 two permanent op...

Страница 5: ...l Venting using a Masonry Chimney and Inside Air Figure 3 Horizontal Venting using Inside Air Table 2 305 TO 457 127 TO 254 VENT PIPE DIAMETER 5 TO 10 12 TO 18 MINIMUM VERTICAL RISE OFF THE TOP OF UNI...

Страница 6: ...ional area of not less than 1 in2 per 7 000 Btuh 310 mm2 per kW up to and including 1 million Btuh plus 1 in2 per 14 000 Btuh 155 mm2 per kW in excess of 1 million Btuh Intake Air Option General Guide...

Страница 7: ...exhaust and combustion air terminals must be installed on the same plane outside wall in order to prevent pressure differences due to prevailing winds In cold climates double wall or insulated inlet p...

Страница 8: ...on Air and Venting Metal Chimney System Shown Figure 7 Combination Air Intake And Venting Masonry Chimney Shown 10 FT 3 1 m 4 FT 1 2 m 5 FT 1 5 m 1 5 FT 0 5 m 5 1 2 FT 1 7 m 1 5 FT 5m 10 FT 3 1 m 3 FT...

Страница 9: ...venting material must be approved for the application Consult the vent manufacturer s product literature GENERAL VENTING GUIDELINES WARNING The vent installation must be in accordance with Part 7 Ven...

Страница 10: ...nector must terminate flush with the inside of the chimney flue Figure 2 Fasten each single wall vent connection with at least 3 corrosion resistant sheet metal screws WARNING Never install a vent pip...

Страница 11: ...a 4 ft 1 2 m horizontal distance is maintained from electric meters gas meters regulators and relief equipment and not less than 7 ft 2 1 m from any adjacent public walkway The bottom of the vent term...

Страница 12: ...ose all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building Turn on clothes...

Страница 13: ...vered under the manufacturer s warranty Excessive pitting and erosion of the internal surface of the copper heat exchanger tubes is NOT covered under the manufacturer s warranty if the result of high...

Страница 14: ...itch The flow switch supplied with the boiler water heater must be wired to the terminal strip in the control panel to prevent the boiler from firing unless there s adequate water flow through the uni...

Страница 15: ...e flow rate required to maintain the desired temperature rise across the boiler heat exchanger The system pump is sized to provide the required flow to the heating system The boiler piping connections...

Страница 16: ...g Check with local codes and ordinances for specific requirements Adjustment Procedure To Maintain Inlet Temperature Above Dew Point T1 Temp Min 110 For Atmospheric T1 Temp Min 125 Sealed Combusion 1...

Страница 17: ...ng must be sized large enough to handle maximum flow through unit 4 All boilers furnished with factory mounted outlet water temperature gauge 5 Boiler pump purging required Use terminals supplied 6 Va...

Страница 18: ...osion of the heat exchanger Water that has a hardness greater than 18 grains per gallon and or a level of dissolved solids exceeding 350 ppm will require a recalculation of the pump size and temperatu...

Страница 19: ...g the warranty The method outlined below can be employed to prevent this condition from occurring A balancing valve should be installed on the outlet side of the water heater for purposes of adjusting...

Страница 20: ...6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Code requires an 1 8 hole in check valve...

Страница 21: ...valve must be installed in the supply piping It should be installed 5 ft 1 5 m above the floor where required by local codes Provide a sediment trap at the bottom of the vertical section of the gas s...

Страница 22: ...trapped in the heating system piping When applicable provisions for vent bleed and gas relief lines must be made in accordance with the latest revision of ANSI Z223 1 NFPA 54 Safe lighting and other p...

Страница 23: ...Table 13 identifies the stages and firing modes associated with the standard single stage units Table 14 identifies the stages and firing modes associated with the two stage option Table 13 Firing Mod...

Страница 24: ...above The FSM will continue to cycle the unit through steps 3 4 and 6 until the unit lights or the demand for heat is removed Main Burner Once the pilot is proven the MV terminal on the FSM is energi...

Страница 25: ...the flame sense module FSM is energized 2 The FSM starts the 10 second ignition trial energizing relay R7 the pilot solenoid valve and the spark generator 3 The pilot valve and spark generator are en...

Страница 26: ...gas is heavier than air and can collect in low areas Propane gas can ignite or explode if an ignition source is present and result in death serious injury and property damage FOR YOUR SAFETY Have only...

Страница 27: ...should match those listed in Table 15 To adjust the differential air pressure see the AIRFLOW ADJUSTMENT instructions in the CHECKING AND ADJUSTMENTS section Figure 19 Manual Valve Manifold Pressure T...

Страница 28: ...faut proc der l entretien 3 Fermer la vanne manuelle d arr t d alimintation de gaz CHECKING ADJUSTMENTS 1 With the burners in operation close the manual shutoff valve in the gas supply line As soon a...

Страница 29: ...b to the off position Figure 18 3 Observe the pilot flame through one of the observation ports located at the left and right ends of the unit For L600 L2300 1 Remove the upper front jacket panel 2 Tur...

Страница 30: ...pressure switch confirms proper air flow These time delays are set within the separate time delay board connected to the relay board PROPANE GAS Optimum results are obtained when the boiler water heat...

Страница 31: ...lem resolved before the boiler water heater is returned to service 7 If there are no signs of damage sooting or corrosion reassemble the unit following the previous steps in reverse order 8 A badly co...

Страница 32: ...heat exchanger out of the unit 10 Remove the V baffle straps and V baffles 11 Thoroughly inspect the heat exchanger for signs of damage If there is no damage clean the heat exchanger with water from a...

Страница 33: ...ter at normal system pressure If it does contact a qualified service technician to have it inspected NEVER try to clean or repair the relief valve If the valve fails to operate properly have it replac...

Страница 34: ...as From Unit shown in connection diagram No Power To Blower s Blower s not plugged in Plug in blower s Defective blower timer TD3 Replace Blower Timer TD3 Blower s malfunctioning Replace blower s Uni...

Страница 35: ...rating control set too low Increase control temperature setting Unit Consistently Shuts Down High limit set too low Increase high limit setting On High Limit Bad Combustion Insufficient air Check CO C...

Страница 36: ...LCD INSTALLATION AND OPERATION INSTRUCTIONS Page 36 RIOM 23 REV B Figure 23 Exploded View...

Страница 37: ...106 1 1 70 3107 1 1 1 70 3108 1 1 70 3109 1 1 70 3110 1 1 3 Jacket Left Panel 03 2155 1 1 1 1 1 1 1 03 1822 1 1 1 1 Jacket Left Panel SS 03 2155 1 1 1 1 1 1 1 1 03 1822 1 1 1 1 1 4 Junction Box Assemb...

Страница 38: ...1 03 1802 1 03 1803 1 03 1804 1 03 1806 1 03 1807 1 1 03 1808 1 03 1809 1 03 1810 1 Jacket Top Panel SS 03 1801 1 1 1 03 1802 1 1 03 1803 1 1 03 1804 1 1 03 1806 1 1 03 1807 1 1 1 03 1808 1 1 03 1809...

Страница 39: ...1 1 1 1 1 1 Comb Chamber Lower Right Side Panel 70 2773 1 1 1 1 1 1 1 1 1 1 1 18 Comb Chamber Upper Left Side Panel 70 2770 1 1 1 1 1 1 1 1 1 1 1 Comb Chamber Upper Right Side Panel 70 2771 1 1 1 1 1...

Страница 40: ...t Orifice NG 10 0089 1 1 1 1 1 1 1 1 1 1 Pilot Orifice LP 10 0090 1 1 1 1 1 1 1 1 1 1 Pilot Orifice NG 10 0093 1 Pilot Orifice LP 10 0120 1 30 Burner Tube 10 0275 2 3 5 7 9 13 15 17 19 25 27 Burner Tu...

Страница 41: ...4 4 4 6 6 6 NS Heat Exchanger Support Channel 03 2022 1 03 2023 1 03 2024 1 NS Tube Replacement Assembly 70 3080 2 2 70 3081 2 70 3082 2 70 3083 2 70 3085 2 70 3086 2 36 O Ring Inlet Outlet Return Hea...

Страница 42: ...1 1 1 1 1 1 49 Manual Shut Off Valve 1 11 0465 1 1 Manual Shut Off Valve 1 1 4 11 0466 1 1 Manual Shut Off Valve 1 1 2 11 0467 1 1 1 Manual Shut Off Valve 2 11 0454 1 50 Flame Sensor UTC 1003 Ignition...

Страница 43: ...idewall Vent Kit HS5 12 0002K1 1 1 1 NS Sidewall Vent Kit with air intake hood HS1 12 0009K 1 1 Sidewall Vent Kit with air intake hood HS2 12 0010AK 1 Sidewall Vent Kit with air intake hood HS2 12 001...

Страница 44: ...DED IS VENT VERTICAL THROUGH THE ROOF OUTDOOR AIR SENSOR INSTALLED WIRED IS VENT THROUGH THE WALL ARE UNITS RACKED IS POWER VENT INSTALLED AND WIRED IS RACK ASSEMBLED TIGHTLY SEALED COMBUSTION NO HOLE...

Страница 45: ...stion Air Damper Power Vent Proving Switch Barometric Damper COMMISSIONING THE UNIT Customer Instructed Yes No All Covers Replaced Yes No Wiring Secure Tight Yes No Customer Given Manual Yes No Cabine...

Страница 46: ...de wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adjacent...

Страница 47: ...structions for the installation of the venting system design or the venting system components and 2 A complete parts list for the venting system design or venting system d MANUFACTURER REQUIREMENTS GA...

Страница 48: ...hrough the tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemical freon dry cleaning chemicals degre...

Отзывы: