manualshive.com logo in svg
background image

AS0715-E

Page 

1

 

WATER SOFTENER

SERIES 500

12 DAY TIMER

INSTALLATION & OPERATING

INSTRUCTIONS

Model :

 

AS0715-E

Serial No :

      ………………………..

            Telephone: (07) 3219 2233 

Facsimile: (07) 3219 2266

Email: [email protected]                      Website: www.ibcwater.com.au

FILTRATION & WATER TREATMENT PRODUCTS
for commercial, industrial and residential application

Manufacturer and Supplier of

Содержание 500 series

Страница 1: ...OPERATING INSTRUCTIONS Model AS0715 E Serial No Telephone 07 3219 2233 Facsimile 07 3219 2266 Email sales ibcwater com au Website www ibcwater com au FILTRATION WATER TREATMENT PRODUCTS for commercial...

Страница 2: ...imately 20ppm based on a sample volume of 10mls Other hardness test kits are available for more accurate testing eg Hardness Tablets Directions Take a 50ml sample of water in a screw capped bottle Add...

Страница 3: ...ms call C 3 Daily Water Usage in litres call D For household situations allow 250 litres per person per day CALCULATION N 1000 x C D x H Select nearest lower whole number If necessary consult your dea...

Страница 4: ...e system pressure must be between 140 kPa and 690 kPa psi 5 If the system pressure is greater than 690kPa psi a pressure reducing valve must be installed 6 The unit must be installed in accordance wit...

Страница 5: ...Again turn knob B counter clockwise until cam follower G has fully depressed drain valve stem H Water will run from drain line and water in the salt storage tank will be lowered approximately to the...

Страница 6: ...enerations select tabs 1 3 5 7 9 11 From the left column locate the number in the family reading along and down from the hardness column where the column intersect gives the number of regenerations fo...

Страница 7: ...AS0715 E Page 7...

Страница 8: ...AS0715 E Page 8 Water Conditioning Control System Installation Operating and Maintenance Manual 541 030 VALVE...

Страница 9: ...repare the resin bed for brining In brine draw concentrated salt brine is drawn from the brine tank and directed to flow down through the riser tube and up through the resin bed to the drain Brine is...

Страница 10: ...e appears in the window Note A M or P M Set Time of Day 1 Remove the front dust cover from the timer assembly 2 Turn the Timer Knob B until the alignment mark located on the Time of Day Gear C points...

Страница 11: ...15 87 Screw Head Mount 4 15 529 239 1 Cycle Cam Knob Assembly 1 16 529 219 3 Drain Plunger Assembly 1 17 401 7 return Spring Drain Plunger 1 18 185 0221 1 O ring Plunger Cap 1 19 529 286 Plunger Cap 1...

Страница 12: ...AS0715 E Page 12...

Страница 13: ...1 19 186 111 N O ring Brine Fitting 1 20 541 250 1 Brine Fitting 1 21 19 19 C Clip Backwash Flow Adjuster 1 22 541 243 Backwash Flow Adjuster w o rings 1 23 529 244 Gasket Cross Over Port 1 24 541 244...

Страница 14: ...AS0715 E Page 14...

Страница 15: ...ently c Faulty safety float a Verify that the safety float is properly set b Check regeneration frequency c Replace safety float 4 Loss of resin a Faulty air check in storage tank b Leak at the distri...

Страница 16: ...he timer assembly 6 Follow these steps in reverse to reinstall the timer assembly Main Diaphragm Replacement 1 Disconnect all electrical power to the control 2 Place the bypass valve into the bypass p...

Страница 17: ...wer to the control 2 Place the bypass valve into the bypass position 3 Relieve system pressure 4 Disconnect the solenoid cable from the solenoid coil 5 Remove the four 4 screws from the backcap 6 Plac...

Страница 18: ...Lightly lubricate the o rings with a Dow 111 Silicone based lubricant 11 Follow these steps in reverse to re install the backwash adjustment valve Solenoid Assembly Replacement 1 Disconnect all elect...

Страница 19: ...r Cabinet Model Float Distance X AS0715 E 100mm AS0922 E 200mm AS1029 E 260mm Adjustment of Softener Brine Valve 1 Lift float rod to full up position 2 Set float to distance shown Measure from the top...

Отзывы: