Modbus
88
MI3
15
Modbus
The Modbus protocol follows the master/slave model. One master controls one or more slaves.
Typically, the master sends a request to a slave, which in turn sends a response. The request/response
mechanism is called a transaction. Requests and responses are also referred to as messages.
Specification:
Version:
Modbus serial line (RS485)
Mode:
RTU (Remote Terminal Unit)
Physical layer:
RS485, 2 wire, electrically isolated
Baud rate:
9.6, 19.2, 38.4, 57.6, 115.2 kBit/s
Connection
terminal
Address range:
1 to 247 (for the Modbus device)
Parity
even
The detailed Modbus specification can be found under
15.1
Wiring
15.1.1
Comm Box (metal)
X1 Pin Terminal
Modbus
1
D0
(negative signal)
2
D1
(positive signal)
3
Shield
4
GND
(output, used for external termination)
5
n.a.
6
+ 5 V
(output, used for external termination)
L
ED
,
yellow
ON while communicating
L
ED
,
red
Error
Figure 76: Modbus Terminal for Comm Box (metal)
The termination for Modbus networks must be realized externally by the user!