Profibus
80
MI3
14
Profibus
Profibus DP-V0 defines a cyclical data exchange between a master (e.g. a PLC) and a slave (MI3
sensor). At start-up first an array of parameters (Profibus specific data) is sent from the master to the
slave, followed by an array with the configuration (sensor specific presetting’s taken from the GSD
file) also sent from the master to the slave.
After start-up the bus switches to the data exchange state. In this state in- and output data gets
exchanged cyclically between master and slave. The
input data
is sent from the slave to the master
and contains mainly the measured temperatures of the MI3 sensor, see section 14.2.2
page 84. The
output data
is sent from the master to the slave and contains a set of selected sensor
parameters, see section 14.2.3
, page 85. In case of an error in start-up phase or during
data exchange
diagnostic data
is sent to the master, see section 14.2.4
Each Profibus device comes with a device description file (GSD file) which is read by the
programming software of the master to define the slave.
Specification:
Version:
Profibus DP-V0
Physical layer:
RS485, 2 wire, electrically isolated
Baud rate:
9.6 kBit/s to 12 MBit/s (automatic negotiated)
Connection
terminal or Sub-D or M12
Address range:
1 to 125 (for the Profibus device)
ID
0D36
GSD file
“RAY_0D36.gsd“
Head support
up to 8 sensing heads (MI3 or MI3100)
14.1
Wiring
14.1.1
Comm Box (metal)
X1 Pin Terminal
Profibus
1
A
(negative signal)
2
B
(positive signal)
3
Shield
4
GND
(output, used for external termination)
5
n.a.
6
+ 5 V
(output, used for external termination)
L
ED
,
yellow
Blinking: 0.5 Hz: parameters / 1 Hz: configuration
L
ED
,
red
ON: data-exchange
Figure 69: Profibus Terminal for Comm Box (metal)
1.800.868.7495
Содержание MI3
Страница 2: ...1 800 868 7495 info Raytek Direct ca...
Страница 9: ...20 NOTES 119 1 800 868 7495 info Raytek Direct ca...
Страница 73: ...Accessories MI3 Rev F1 05 2013 73 Figure 66 Protective Window 1 800 868 7495 info Raytek Direct ca...
Страница 113: ...ASCII Programming MI3 Rev F1 05 2013 113 1 800 868 7495 info Raytek Direct ca...
Страница 119: ...Notes MI3 Rev F1 05 2013 119 20 Notes 1 800 868 7495 info Raytek Direct ca...