87
VIEW Menu Tables
1.
VIEW > 3D System View
3D System View Screen (view only)
ITEM
DISPLAYS
NOTES
Plant Rate
% firing rate of installation
May differ from firing rate if > 1 heater is connected
Inlet Temp
S2 inlet water temp in °C
-
Outlet Temp
S1 outlet water temp in °C
-
Outdoor
tN4 or outdoor air sensor S4 temp in °C
Only avail Target Mode para = RSET
S6
– Ind Supply
Indirect flow line water temp in °C
Only avail if Operation Mode para = 3
DHW Supply
Domestic hot water tank S5 water temp in °C
Only avail if Operation Mode para = 2 or 3
Tank
Domestic hot water tank S3 water temp in °C
Only avail if heater is a W model
Target
Current target water temp
(2)
Displays '_ _' if there is no target temperature
System Supply
Current S3 system supply water temp in °C
Only avail if heater is a H model
2.
VIEW > Master Info
The master info screen displays the same information as the 3D system view screen plus the additional
items listed in the following table.
Master Info Screen (view only)
ITEM
DISPLAYS
NOTES
Delta Temp
Outlet water temp S1 minus inlet water temp S2
in °C
Temperature rise across the heat exchanger
Ignition Status
Idle (no CFH), Prepurge, IgnTry1 (trial for
ignition), Burn (burner on), Postpurge, HardLock
(hard lockout), SoftLock (soft lockout)
SoftLock = A soft lockout has occurred that
interrupted the heating cycle. The CFH will
resume after fault correction & expiry of 16 min
Firing Rate
% firing rate of burner
% modulation level determined by PIM
Outdoor Hi / Lo
Highest/Lowest recorded temp for sensor S4
Only avail Target Mode para = RSET
Inlet Hi / Lo
Highest/Lowest recorded temp for sensor S2
-
Outlet Hi / Lo
Highest/Lowest recorded temp for sensor S1
-
System Hi / Lo
Highest/Lowest recorded temp for sensor S3
-
Indirect Hi / Lo
Highest/Lowest recorded temp for sensor S5
Only avail if Operation Mode para = 2 or 3
Pump run times
System, boiler and DHW pump total run times
DHW pump for Operation Modes 2 and 3 only