96
2.
TOOLS > Touch Screen Setup
Touch Screen Setup Screen. Items can only be adjusted/used if VERSA control board DIP switch 1 is ON (up)
ITEM
DISPLAYS
NOTES
Brightness
Adjusts screen brightness
Tap and move slide bar to desired setting
Timeout
Adjusts screen timeout i.e. time till blank
screen from last button press
Tap and move slide bar to desired setting
Page Timeout
Adjusts page timeout
Tap and move slide bar to desired setting
3D System View
Tap to navigate to 3D system view home page
-
4.
TOOLS > Clock Setup
Clpock Setup Screen. Items can only be adjusted/used if VERSA control board DIP switch 1 is ON (up)
ITEM
FUNCTION
NOTES
→
Moves flashing adjustment (item) location
Tap to change flashing item location
–
Decreases flashing item
Tap to decrease flashing item
+
Increases flashing item
Tap to increase flashing item
Save
Saves all items displayed
Tap to save all items displayed
Cancel
Cancels all items changes prior to saving
Tap to cancel all items entered prior to saving
Freeze Protection
To enable freeze protection, dip switch position 7 (on the PIM™) must be turned on (UP position).
This is the default position.
If the water temperature drops below 7 °C on the Outlet or Inlet sensors, the water heater pump is
enabled. The pump is turned off when both the Inlet and Outlet temperatures rise above 10 °C
If either the Outlet or Inlet temperature drops below 3 °C, the VERSA starts the burner at the
minimum firing rate. The burner cycle will terminate when both the Inlet and Outlet temperatures rise
above 6 °C.