Ravenheat CSI 85 Скачать руководство пользователя страница 13

SIZING OF ADDITIONAL EXPANSION VESSELS: TABLE 3

Deduct from the value given in the table the 7 litre vessel supplied.

Safety

valve setting (bar)

3.0

Vessel charge
pressure (bar)

0.5

1.0

1.5

Initial System

.

pressure (bar)

0.5

1.0

1.5

2.0

1.0

1.5

2.0

1.5

2.0

Total water

content Of system

EXPANSION VESSEL VOLUME (LITRES)

Litres

2 5

2.1

3.5

6.5

13.7

2.7

4.7 10.3

3.9

6.3

5 0

4.2

7.0

12.9

27.5

5.4

9.5 20.6

7.6

16.5

7 5

6.3

10.5

19.4

41.3

6.2

14.2 30.9

11.7

24.6

19.0 41.2

100

6.3

14.0

25.9

55.1

10.9

15.6

33.1

125

10.4

17.5

32.4

66.9

13.6

23.7 51.5

19.5

41.3

150

12.5

21.0

36.6

62.6

16.3

26.5 61.6

23.4

49.6

175

14.6

24.5

45.3

96.4

19.1

33.2 72.1

27.3

57.9

200

16.7

26.0

51.6

110.2

21.6

36.0 62.4

31.2

66.2

225

16.7

31.5

56.3

124.0

24.5

42.7 92.7

35.1

74.5

250

20.6

35.0

64.7

137.7

27.2

47.5 103.0

39.0

62.7

275

22.9

36.5

71.2

151.5

30.0

52.2 113.3

42.9

91.0

300

26.0

42.0

77.7

165.3

32.7

57.0 123.6

46.6

99.3

325

27.0

45.5

64.1

179.1

35.7

61.7 133.9

50.7

107.6

350

29.1

49.0

90.6

192.6

36.1

66.5 144.2

54.6

115.6

375

31.2

52.5

97.1

206.6

40.9

71.2 154.5

56.5

124.1

400

33.3

56.0

103.6

220.4

43.6

76.0 164.6

62.4

132.4

425

35.4

59.5

110.1

239.2

46.3

80.7 175.1

66.3

140.7

450

37.5

63.0

116.5

247.9

49.0

65.5 165.4

70.2

146.9

475

39.6

66.5

123.0

261.7

51.6

90.2 195.7

74.1

157.2

500

41.6

70.0

125.9

275.5

54.5

95.0 206.0

76.0

165.5

For system volumes

other than those given

above, multiply the

0.0633

0.140

0.259

0.551

0.109

0.190 0.412

0.156

0.331

system volume by
the factor across

Note: This pressure can be increased up to 1.5 bar to suit high static head situations, see item 10, other appliance components in the

SERVICING INSTRUCTIONS.

B) Where fitting a make up vessel would be

difficult re pressurisation of the system can

be done. See section on FILLING.
If the capacity of the central heating system

should exceed 110 litres, an additional ves-
sel should be installed on the return to the
combination boiler from the heating system

(Fig. 7). Guidance on vessel sizing is given
in (Table 3).
Reference should be made to British Gas
Publications <<Material and Installation
Specifications for Domestic Central Heating
and Hot Water>>,. Draining taps should be at
least 1/2" in BSP nominal size and be in

accordance with BS 2879.

It is most important that the correct concen-

tration of the water treatment product is
maintained in accordance with the manufac-
turers’ instructions.

If the boiler is installed in an existing system

any unsuitable additives MUST be removed

by thorough cleansing.
BS 7593:1992 details the steps necessary

to clean domestic central heating system.

Also check pipework and renew any corrod-
ed pipework or fittings. Valve glands must be
repacked or replaced wherever necessary
and any defective controls exchanged.

WATER TREATMENT

This boiler has a secondary ALUMINIUM

4.6.9

Installation to an existing central heat-

ing system

The combination boiler is designed to oper-
ate on a sealed system only. Therefore if the
existing system is of the open water type it
will have to be modified to comply with BS

5376 Part 2.

Before installing a new combination boiler to

an existing system, flush out the old system
with a recommended descaling agent.

alloy heat exchanger Ravenheat recom-

mended

only

the use of FERNOX-COPAL or

SENTINEL Xl00 water treatment products,

which must be used in accordance with the

manufacturers instructions. For further infor-
mation contact:
Fernox Manufacturing Co. Ltd.

Tel. 01799 550811

Sentinel Division Betz Dearborn Ltd.
Tel. (0151) 424 5351

14

Содержание CSI 85

Страница 1: ...gdom Water Fitting Byelaws Scheme WITH TIMER NATURAL GAS G 20 I2H G C N0 47 581 20 LPG G 30 G 31 I3 G C N 0 47 581 24 INSTALLATION AND SERVICING INSTRUCTIONS TO BE LEFT WITH USER Technical and illustr...

Страница 2: ...domestic hot water Highly reliable diverter valve with ethylene propylene diaphragm permitting primary flow circulation in the boiler during domestic hot water supply Built in frost protection Printe...

Страница 3: ...or D H W water 3 Burner 4 Ignition pilot burner 6 Condensing heat exchanger 7 Ignition board 9 ignition electrode 11 Frame 12 Modulating gas valve 15 Heating control 16 Hot water control 17 D H W sens...

Страница 4: ...12 Modulating gas valve 26 Auto air vent valve 15 Heating control potentiometer 16 Hot water control potentiometer 27 Pressure switch giving priority 28 Pressure switch 17 Water pressure switch 18 Ov...

Страница 5: ...tial heating requirements between domestic hot water tap is turned on the boiler maximum and minimum settings will function in the following sequence 2 3 2 Air is drawn by the fan for combustion 2 2 1...

Страница 6: ...at 2 4 5 3 1 OVERALL DIMENSION 3 1 2 When D H W is no longer called for the boil er automatically returns to the central heat ing mode Switch 33 in the summer position The boiler functions like an aut...

Страница 7: ...TLET CONNECTION D H W 15 mm copper pipe SAFETY DISCHARGE C H 15 mm copper pipe CONDENSATION DRAIN 3 4 21 5 mm push fit over flow MAX COLD WATER CAPACITY WITHOUT ADDITIONAL EXPANSION VESSEL 110 LITRE S...

Страница 8: ...D H W OUTLET CONNECTION D H W 112 RC 22 mm compression isolating valve 22 mm compression isolating valve 15 mm compression isolating valve 15 mm copper pipe SAFETY DISCHARGE C H 15 mm copper pipe COND...

Страница 9: ...ding 60 kW BS 5440 2 Ventilation for gas appliances of rated input not exceeding 60 kW DD 189 1990 Discharge of condensate Health Safety Document No 635 The Electricity at Work Regulations 1989 The ma...

Страница 10: ...es Installation pipes should be fitted in accordance with BS 6891 Pipework from the meter to the boiler must be of adequate size 22 mm min To within at least 3 metre of the boiler 15 mm min can then b...

Страница 11: ...189 1990 The drain outlet on the boiler is standard 3 4 21 5 mm push fit overflow pipe NOTE Condensate drain pipework must never be less than 15 mm Important any external runs must be car ried out in...

Страница 12: ...ormal operation of the system if automatic water make up is required Booster pump method Fig 8 The system may be filled through a self con tained unit comprising of a cistern pressure booster pump if...

Страница 13: ...Where fitting a make up vessel would be difficult re pressurisation of the system can be done See section on FILLING If the capacity of the central heating system should exceed 110 litres an additiona...

Страница 14: ...petent person and be in accordance with the current I E E Regula tions and local regulations which apply The Ravenheat boiler is supplied for con nection to a 230 V 50 Hz single phase sup ply The supp...

Страница 15: ...mplete with 1 2 brass nuts and washers 2 22 mm flanged copper tails complete with 3 4 brass nuts and washers Box 2 of 2 containing Fig 12 Horizontal CSI flue kit 56 Flue gas sample point 57 Flue bend...

Страница 16: ...5 3 Fig 15 1 Open the top of the carton Fig 16 2 Rest the carton on the floor keeping the flaps open Fig 18 4 Rest the boiler on the floor and remove the polystyrene guards Fig 19 1 7...

Страница 17: ...the appliance to release them from their upper suspension hooks Fig 26 27 Fig 25 Make sure the casing and screws are put to one side in a safe place INSTALLING THE APPLIANCE FOR REAR FLUE OUTLET Fig 2...

Страница 18: ...equal to W 152 mm Must be de burred Cut the inner flue duct 60 mm at right angles to a length equal to W 264 mm Insert from cut end Reassemble the two tubes Insert centering spring 65 Must be de burre...

Страница 19: ...ng bolts Working above the boiler pull the flue exhaust duct towards the boiler in order to engage tube 61 into its header 57A Position flue into elbow header and push so as to locate inner and outer...

Страница 20: ...ble from Ravenheat Manufacturing and should be used to support flue length at least every 1 8 metre preferably at each joint this bracket should be secured to wall and flue duct INLINE FLUE BEND Meas...

Страница 21: ...ht angles and to a length equal to W Y 47 mm Fig 32 Cut the inner flue duct 60 mm dia at right angles and to a length equal to W Y 65 mm Outer air duct and inner flue duct must be de burred 5 7 12 VER...

Страница 22: ...pplication Additional 1000 mm approx Flue Extension pieces as necessary each extension is provided with inlet and outlet sealing rings and flue centering bracket One box containing straight header wit...

Страница 23: ...ocated Fig 44 Make sure that the entire flue is adequately supported Use at least one bracket for each extension used Ensure that all inner flue connections have a good fit seal and that the space cli...

Страница 24: ...ts or wiring The discharge must not be over an entrance or a window or any other type of access ELECTRICAL CONNECTIONS IMPORTANT Electricity supply must be as specified in clause sect 4 10 When contro...

Страница 25: ...connection to the central heating system until water is heard to flow Starting with the lowest radiator open each air release tap in turn Close it only when clear water free of bubbles flows out In t...

Страница 26: ...27...

Страница 27: ...528 and envelop the spark electrode tip 6 10 6 11 6 12 ADJUSTING MINIMUM AND MAXIMUM PRESSURE Fig 51 SIT HONEYWELL GAS VALVE Remove cap covering modulator to gas valve Detach one of the cables connec...

Страница 28: ...ferential pressure 2 8 Lts min 0 61 gals min The temperature of the water will depend on the rate at which it flows If due to high water pressure the flow rate is too high and thus the temperature too...

Страница 29: ...on pipe 18 Heat exchanger 24 Main burner 25 Pilot burner 27 Auto air vent valve 28 Pressure switch 29 Seal 31 Seal 37 Window seal 42 Window clamp ring 44 Fan 46 Header gasket 50 Flue gas exhaust hood...

Страница 30: ...epend upon the particular installation conditions and usage but in general once year should be adequate 7 2 7 2 1 7 2 2 7 2 3 7 2 4 7 2 5 7 2 5 1 Before the start of any servicing or replacement of co...

Страница 31: ...TO REMOVE REPLACE THE FAN nt cover the fan motor from Support the fan and remove the two fixing screws and bracket from the front of the flue hood Carefully withdraw from condensing heat 7 6 5 TO REM...

Страница 32: ...63 7 812 Pull the heat exchanger up until its flow connections come out from the combustion chamber and then remove it Fig 64 7 8 13 Replace in reverse order Ensure correct wire position Fig 94 IMPOR...

Страница 33: ...7 10 7 10 1 TO REPLACE THE ELECTRODE Fig 66 Remove front casing sect 7 3 Remove combustion chamber front cover sect 7 4 Fig 56 Fig 60 TAKE OFF Fig 62...

Страница 34: ...ont cover sect 7 3 7 4 Remove the lower grating sect 5 4 2 Fig 21 Release the fitting that secures pilot pipe at the gas valve Remove electrode sect 7 10 Unscrew pilot connection from pilot burner Pul...

Страница 35: ...ner assembly as described in sect 7 13 Unscrew the union Fig 70 Unscrew the 4 screws securing the injector manifold to the burner Fig 71 Pull the manifold up and out from the combustion chamber Fig 72...

Страница 36: ...asten the instrument panel Fig 23 Lift the instrument panel to detach it from the sides and lower it down by rotating it on its own hinges Fig 25 7 16 4 Pull the 2 wires from the Modulator Remove the...

Страница 37: ...ve the three wires that connect to the overheat thermostat making sure that these wires will subsequently be reconnected to the same poles Fig 94 7 25 1 Remove the split pin and pull the thermostat se...

Страница 38: ...2 Close the on off valves for the heating circuit and the hot water circuit Drain the boiler at drain point Fig 93 and drain hot water from the lowest hot water tap and drain point on DHW inlet cock...

Страница 39: ...ve the two sides of the casing sect 5 4 5 Close the on off valve on the domestic cold water central heating and gas supply Drain domestic water from the lowest hot water tap and drain point on DHW inl...

Страница 40: ...93 Unscrew the screw from its body clean or replace Replace in reverse order Fill the system as described in the sect 6 4 6 5 and check for leaks TO REMOVE REPLACE TIME CLOCK Fig 88 A Remove the front...

Страница 41: ...nd drain hot water from the lowest hot water tap and drain point on DHW inlet cock Fig 46 Unscrew the four nuts that connect the DHW heat exchanger and pull it out from boiler If necessary the pipes f...

Страница 42: ......

Страница 43: ...Section 8 FAULT FINDING CENTRAL HEATING Switch on Select Winter Central Heating Stat to maximum Ensure external controls calling for heat Room Stat Time Clock TRV...

Страница 44: ...FAULT FINDING DOMESTIC HOT WATER Before continuing it may be necessary to see Central Heating Fault Finding Select only Summer Domestic Hot Water Open Domestic hot tap close to appliance 45...

Страница 45: ...SECTION 9 ELECTRICAL SYSTEM DIAGRAM Fig 94 46...

Страница 46: ...47...

Страница 47: ......

Страница 48: ...49...

Страница 49: ...end 90o 14 flue exhaust duct 11 air inlet terminal 14 air intake duct 12 flue exhaust terminal 15 two way flue gas header 13 45o air intake bend 16 vertical eccentric flue exhaust duct Supplied with t...

Страница 50: ...clips are available on request should they be required NOTE for eccentric vertical flue a 125 mm 5 in diameter flashing plate will be required 135 M F bend consisting of 135 elbow with 0 ring side F 8...

Страница 51: ...exhaust inlet pipe 18 metre Minimum distance D I E 1 5 metre Min inlet pipe distance 0 5 metre Min distance between pipe 50 mm NOTE The pressure loss for each elbow fitted is 90o slow bend less 3 met...

Страница 52: ......

Страница 53: ...9 371267 E23 732 E23 730 372842 E23 715 371268 E23 716 E23 733 372845 E23 718 E24 630 372849 173100 372 866 372894 E23 731 E23 735 371271 372888 372851 372867 173101 378864 E23 737 E23 738 E23 720 372...

Страница 54: ...895 371273 371310 372896 371274 372874 372897 E23 724 372875 E24 629 E23 750 E23 751 E23 752 Description Depression chamber Nozzle 0 27 for natural gas Nozzle DM 0 22x1 LPG Ignition electrode Cable f...

Страница 55: ...Chartists Way Morley Leeds LS27 9ET Telephone 0113 252 7007 Tfax 0113 238 0229...

Отзывы: