background image

Page 10 of 22

IN052   Rev. K   0613

INSTALLATION INSTRUCTIONS

1

2

2.3. Plumbing Hook-up

All plumbing should be performed in accordance 

with Local and State Codes by a Qualified Plumber.

1. 

Shut off water main valve located after the pres-

sure tank.

2. 

Drain water line.

3. 

Plumb system into water line after the pressure 

tank and all other water treatment equipment. 

(Exception: Install before activated carbon filter/

tank.)

4. 

Plumb appropriately to “Water In” and “Water 

Out”. (Figure 6) 

For ease of installation and servicing a ¾” sharkbite 

fitting is provided on the inlet. This is compatible 

with 3/4” pex or copper tubing.

5. 

From the open leg of the inlet tee run pipe/tubing 

thru a bypass valve to a second tee.

6. 

Plumb unit as shown in Figures 6, 7 and 7a. The 

Bladder Tank must be connected to the Rise Leg 

of the Tee provided on the System Outlet, without 

any elbows between the Tee and Tank.

Warning: An undersized bladder tank will result in 

premature pump failure.
Note: Pipe supports are required, particularly to 

support the bladder tank. These are not shown, as 

installation details vary by property.

7. 

Plumb the water line to the house into the open 

leg of the second tee. (Figure 7) It is recommended 

that a flow control valve be installed in this line. 

8. 

The built-in pump pressure switch and pressure 

regulator provided are designed for use with a 

pressure tank. The pressure tank bladder pressure 

should be set per the tank manufacturers recom-

mendations for a pressure switch setting of 37 psi.

9. 

An outlet pipe must be installed in the overflow 

connection (figure 6) and connected to drain or 

sump in accordance to Local and State Codes.

Warning: Overflow may occur due to a blocked vent 

pipe, debris in or wear of the solenoid valves, or incorrect 

connection to the electrical supply. Failure to connect 

the overflow to a drain or sump (with sump pump or 

other means of external discharge) may flood the area 

around the unit in the event of overflow occurring. 

10. 

With the system in bypass mode, slowly open the 

main water valve and check for leaks.

11. 

Remove tank cover and slowly change bypass 

valve to service configuration and check for leaks.

Figure 6 - Rear View, Unit Only

Figure 7 - Water Connections

Figure 7a - Water Connections

Overflow, connect to 

drain or sump per local 

and state codes

Outlet Tee provided with Unit. 

Bladder Tank to be connected to

Tee Rise Leg. Do not install bends

between Tank and Tee.

Bladder tank 

Minimum capacity 

5 Gal. (Required)

Outlet valve

(Recommended)

Pressure gauge

(Optional)

Inlet valve

(Recommended)

Water out, to house

Flow control valve

(Recommended)

Bypass valve

(Recommended)

Existing house 

pressure tank

(Tank tee, pressure switch, 

pressure gauge and relief 

valve not shown.)

Water in, 

From well pump

Vent hole, breaks 

siphon if unit overflows.

To bladder tank

Water in

Water out

Overflow, to be 

connected to drain 

or sump

Содержание AIRaider EZ95

Страница 1: ...AIRaider EZ95 Installation Instruction Manual RadonAway 3 Saber Way Ward Hill MA 01835 radonaway com IN052 Rev K 0613...

Страница 2: ...Check 3 RETESTING 4 MAINTENANCE 4 1 Six Month Service recommended 4 2 Annual Service required 5 TROUBLE SHOOTING 6 ALARM SCHEMATIC 7 BLOWER BRUSH REPLACEMENT 8 EQUIPMENT SPECIFICATION LIMITED WARRANTY...

Страница 3: ...afety 2 Installation site requirements 3 Inspection of System components 4 Qualified Technicians are necessary 5 Knowledge of all contaminants in the water 1 1 Safety Matters Safety is the most import...

Страница 4: ...he system output the AIRaider EZ95 may run dry which will cause the pump installed integrally within the AIRaider EZ95 System to automatically shutdown To prevent outflow interruptions it is strongly...

Страница 5: ...tem or the AIRaider EZ95 System Failure to remove other contaminants can reduce the effectiveness of the system and may result in system damage 1 3 Full Water Test A full Water Sample Analysis must be...

Страница 6: ...5 System in accordance with the installation instructions Check your Local and State Code and Licensing requirements Failure to follow the instructions may lead to poor system performance and or possi...

Страница 7: ...Raider EZ95 System are listed below Read all components of each step prior to beginning the actual installation 1 System Location 2 Readying the System for Installation 3 Plumbing Hook Up 4 Electrical...

Страница 8: ...ing necessary this is typically in proximity to the well tank 2 Electrical Hook up Keep in mind the need for accessibility to a 20 Amp dedicated 120VAC power supply 3 Exhaust Line Venting The location...

Страница 9: ...r level Pump float 3 Cable length tether to float normally open prevents pump dry running Vent On off float Float switch hose clamp Check valve behind pressure regulator Vent pipe hose clamps Push but...

Страница 10: ...gned for use with a pressure tank The pressure tank bladder pressure should be set per the tank manufacturers recom mendations for a pressure switch setting of 37 psi 9 An outlet pipe must be installe...

Страница 11: ...N C Blower Neon Lamp Push Button Thermostat Over Ride A B 1 2 C D E Blower Enclosure Electrical Enclosure Wiring NEZ SRT B G W B W W B B B B W W B B B R R R R W W W R RRG RRG B B W B W B B B B B B B B...

Страница 12: ...tion 4 Ensure that the red lead provided for an optional auxiliary fan remains insulated if not used The red lead is the live feed from the Aeration System to the Fan Warning Do Not connect any of the...

Страница 13: ...st be wired to the system electrical box connections as shown in the Electrical Schematic Figure 8 This will ensure that the fan operates only when required by the system The red lead is the live feed...

Страница 14: ...ystem Start Up 1 Remove cover and lid and pour cup of chlorine into the AIRaider tank This will disinfect the system Secure the lid with the screws and washers provided 2 Check that all plumbing and e...

Страница 15: ...given in Table 1 for the measured well pump output This is done by temporarily attaching a hose to the house connection of the bypass valve and adjusting the flow control valve to provide the correct...

Страница 16: ...should be followed to maintain the AIRaider Check and or clean the blower air intake filter Check and or clean any filters or strainer installed on the inlet line to the AIRaider In installations with...

Страница 17: ...f necessary Clean if necessary tank and diffusers of all mineral build up Chlorinate tank and lines by pouring cup of chlorine into the tank Check all control panel connections and electrical componen...

Страница 18: ...not illuminated Check power switch in on position circuit breaker at panel in on position Check pump float switch for proper operation Check that the pump priming orifice rear left behind pump is not...

Страница 19: ...Page 19 of 22 IN052 Rev K 0613 6 ALARM SCHEMATIC ALARM SCHEMATIC 1 2 3 4 5 6...

Страница 20: ...ve the brush holder assembly from the motor 6 Insert the new brush holder assembly making certain that brass prongs engage the electrical socket and then replace the retaining screw 7 Repeat steps 4 6...

Страница 21: ...0 VAC Buna N Seal Brass Valve Body NPT System Voltage 115V Electric Supply 20 Amp 115VAC Dedicated Circuit Recommended Flow Up to 7 GPM Radon Reduction Up to 95 Water Inlet Outlet Connections Sharkbit...

Страница 22: ...AR PURPOSE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THERE IS NO WARRANTY OF MERCHANTABILITY ALL OTHER WARRANTIES EXPRESSED OR WRITTEN ARE NOT VALID In order to ob...

Отзывы: