background image

Page 14 of 22

IN052   Rev. K   0613

2.6.  Remote Air Intake

If a Remote Air Intake is required because of Air  Quality or Quantity issues then Use Only 1-1/4” or larger 

Schedule 40 PVC or equivalent pipe for the air intake line. 

1. 

Unscrew the air filter provided from the cover and run the intake line from the  pipe thread  

connection on the cover to the location selected for the air intake.

NOTE: A rubber coupling or similar means to disconnect the intake line from the AIRaider™ must be provided so that 

the AIRaider™ cover may be removed for start-up and maintenance.

2. 

Connect the air filter previously removed to the intake end of the intake line.

If the air intake is located outside, the intake must be mounted high enough to prevent the drawing in of snow, water and 

other contaminants. Do not locate the air intake in the vicinity of vents from furnaces, barbecue grills, etc

.

2.7.  System Start-Up

1. 

Remove cover and lid and pour ¼ cup of chlorine into the AIRaider™ tank. (This will disinfect the         

system.) Secure the lid with the screws and washers provided.

2. 

Check that all plumbing and electrical connections have been properly completed.

3. 

Slowly change bypass to the “service” configuration. Check for leaks.

4. 

Turn power switch for AIRaider™ to “On”. Solenoid valves will now open allowing water into the       

system. The aeration process will also start. Check for leaks. 

5. 

Allow the AIRaider™  to fill with water. The aeration process will stop. The pump will self prime 

during the fill cycle. There is an orifice behind the left side of the pump which allows the pump to 

prime. This orifice will spray water into the aeration tank whenever the pump is running. The orifice 

is sized for the minimum flow specified for the pump. (The pump will fail to prime if the orifice is 

blocked). The pump will start and will continue running until the house water system is pressurized. 

Check thoroughly for leaks around all pipe joints, etc., and seal if required. 

INSTALLATION INSTRUCTIONS

1

2

Содержание AIRaider EZ95

Страница 1: ...AIRaider EZ95 Installation Instruction Manual RadonAway 3 Saber Way Ward Hill MA 01835 radonaway com IN052 Rev K 0613...

Страница 2: ...Check 3 RETESTING 4 MAINTENANCE 4 1 Six Month Service recommended 4 2 Annual Service required 5 TROUBLE SHOOTING 6 ALARM SCHEMATIC 7 BLOWER BRUSH REPLACEMENT 8 EQUIPMENT SPECIFICATION LIMITED WARRANTY...

Страница 3: ...afety 2 Installation site requirements 3 Inspection of System components 4 Qualified Technicians are necessary 5 Knowledge of all contaminants in the water 1 1 Safety Matters Safety is the most import...

Страница 4: ...he system output the AIRaider EZ95 may run dry which will cause the pump installed integrally within the AIRaider EZ95 System to automatically shutdown To prevent outflow interruptions it is strongly...

Страница 5: ...tem or the AIRaider EZ95 System Failure to remove other contaminants can reduce the effectiveness of the system and may result in system damage 1 3 Full Water Test A full Water Sample Analysis must be...

Страница 6: ...5 System in accordance with the installation instructions Check your Local and State Code and Licensing requirements Failure to follow the instructions may lead to poor system performance and or possi...

Страница 7: ...Raider EZ95 System are listed below Read all components of each step prior to beginning the actual installation 1 System Location 2 Readying the System for Installation 3 Plumbing Hook Up 4 Electrical...

Страница 8: ...ing necessary this is typically in proximity to the well tank 2 Electrical Hook up Keep in mind the need for accessibility to a 20 Amp dedicated 120VAC power supply 3 Exhaust Line Venting The location...

Страница 9: ...r level Pump float 3 Cable length tether to float normally open prevents pump dry running Vent On off float Float switch hose clamp Check valve behind pressure regulator Vent pipe hose clamps Push but...

Страница 10: ...gned for use with a pressure tank The pressure tank bladder pressure should be set per the tank manufacturers recom mendations for a pressure switch setting of 37 psi 9 An outlet pipe must be installe...

Страница 11: ...N C Blower Neon Lamp Push Button Thermostat Over Ride A B 1 2 C D E Blower Enclosure Electrical Enclosure Wiring NEZ SRT B G W B W W B B B B W W B B B R R R R W W W R RRG RRG B B W B W B B B B B B B B...

Страница 12: ...tion 4 Ensure that the red lead provided for an optional auxiliary fan remains insulated if not used The red lead is the live feed from the Aeration System to the Fan Warning Do Not connect any of the...

Страница 13: ...st be wired to the system electrical box connections as shown in the Electrical Schematic Figure 8 This will ensure that the fan operates only when required by the system The red lead is the live feed...

Страница 14: ...ystem Start Up 1 Remove cover and lid and pour cup of chlorine into the AIRaider tank This will disinfect the system Secure the lid with the screws and washers provided 2 Check that all plumbing and e...

Страница 15: ...given in Table 1 for the measured well pump output This is done by temporarily attaching a hose to the house connection of the bypass valve and adjusting the flow control valve to provide the correct...

Страница 16: ...should be followed to maintain the AIRaider Check and or clean the blower air intake filter Check and or clean any filters or strainer installed on the inlet line to the AIRaider In installations with...

Страница 17: ...f necessary Clean if necessary tank and diffusers of all mineral build up Chlorinate tank and lines by pouring cup of chlorine into the tank Check all control panel connections and electrical componen...

Страница 18: ...not illuminated Check power switch in on position circuit breaker at panel in on position Check pump float switch for proper operation Check that the pump priming orifice rear left behind pump is not...

Страница 19: ...Page 19 of 22 IN052 Rev K 0613 6 ALARM SCHEMATIC ALARM SCHEMATIC 1 2 3 4 5 6...

Страница 20: ...ve the brush holder assembly from the motor 6 Insert the new brush holder assembly making certain that brass prongs engage the electrical socket and then replace the retaining screw 7 Repeat steps 4 6...

Страница 21: ...0 VAC Buna N Seal Brass Valve Body NPT System Voltage 115V Electric Supply 20 Amp 115VAC Dedicated Circuit Recommended Flow Up to 7 GPM Radon Reduction Up to 95 Water Inlet Outlet Connections Sharkbit...

Страница 22: ...AR PURPOSE THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF THERE IS NO WARRANTY OF MERCHANTABILITY ALL OTHER WARRANTIES EXPRESSED OR WRITTEN ARE NOT VALID In order to ob...

Отзывы: