REGULATION INSTRUCTIONS
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4
38
5. REGULATING THE APPLIANCE
5.1 Parameters table
PARAMETER
N°
TYPE OF OPERATION
PARAMETER
VALUE
FUNCTION
P00
Selects the model of boiler
00-06
00 = 13 kW
01 = 18 KW
02 = 25 kW
03 = 28 kW
04 = 34 kW
05 = 55 kW
06 = 100 kW
P01
Selects the type of boiler
00-05
00 = Istantaneous boiler (w/dual
circuit exchanger)
01 = Istantaneous boiler
(w/secondary D.H.W. plate exch.)
02 = Storage cylinder boiler
03 = Boiler with Comfort storage
cylinder
04 = Comfort istantaneous boiler
(w/sec. D.H.W. plate exch.)
05 = Only heating boiler
P02
Selects the type of gas supply
00
01
02
Natural gas
LPG
G25
P03
Sets the central heating temperature
00
01
Standard (30-80 °C)
Reduced (25-45 °C)
P04
Heating output rising time
00-04
00 = 0 seconds (Disabled)
01 = 50 seconds (Default)
02 = 100 seconds
03 = 200 seconds
04 = 400 seconds
P05
Water hammer prevention function
00
01
Off
On
P06
D.H.W priority function
(RS version only - with connection to a remote
storage cylinder)
00
01
Off
On
P07
Central heating timer
00 - 90
Displayed in multiples of 5
seconds
(default value 36 x 5 = 180”)
P08
Central heating pump overrun timer
00 - 90
Displayed in multiples of 5
seconds
(default value 36 x 5 = 180”)
P09
D.H.W/Storage cylinder pump overrun
timer
(RS version only - with connection to a remote
storage cylinder)
00 - 90
Displayed in multiples of 5
seconds
(default value 18 x 5 = 90”)
P10
Sets the minimum fan speed
33 - P11
Displayed in hertz
(1Hz = 30 rpm)
P11
Sets the maximum fan speed
P10 - 203
Displayed in hertz
(1Hz = 30 rpm)