INSTALLATION INSTRUCTIONS
RK 100 - RAD - ING - MAN.INST - 1311.1 - DIGITECH CS MIAH4
23
3.7 Gas Connection
3.7.1 General warnings
The connection to the gas supply must be carried out by professionally qualified personnel in
accordance with relevant standards:
When connecting the boiler to the gas supply pipe, only use appropriate washers and gas fittings. The
use of hemp, Teflon tape and similar materials is not allowed.
The flow rate of the gas meter must be sufficient for the simultaneous use of all devices connected to
it. Connect the generator gas, according to the regulations. The diameter of the gas pipe coming out of
the generator, is not decisive for the choice of the diameter of the hose between the unit and the
meter. It must be chosen in function of its length and load losses as a result of calculation by a
qualified technician. Check the nominal pressure provided to the counter as if insufficient can reduce
the power of the generator with inconvenience to the user.
Before installing the boiler, check the following:
■
The pipe work must have a section appropriate for the flow rates requested and the pipe lengths installed, and
must be fitted with all the safety and control devices provided for by current standards.
■
The gas supply line must be a minimum of a 22 mm diameter pipe with an uninterrupted supply from meter to
boiler and comply with current standards and regulations.
■
Check the internal and external seals of the gas supply system.
■
A gas shut-off valve must be installed upstream of the appliance
■
The gas pipe work must have and bigger or equal section to the one of the boiler.
■
Before starting up the boiler, make sure that the type of gas corresponds to that for which the appliance has
been set-up (see gas type label inside the boiler).
■
The gas supply pressure must be between the values reported on the rating plate (see gas type label inside the
boiler).
■
Prior to installation, it is good practice to ensure that there are no machining residues on the gas supply pipe.