;,BlockErr ; Map BlockErr here since Clx sets to -0xffffffff on Connection Failure
;,m31>1[1],b01_OutMon, ; Ofs= 2 Len= 1 IC660BBR101 16-Ckt Normally-open Relay Block
;,m31>2[1],b02_OutMon, ; Ofs= 3 Len= 1 IC660BBD020 24/48VDC 16 Ckt Source I/O Block
;,m31>3[2],b03_OutMon, ; Ofs= 4 Len= 2 IC660BBA020 24/48VDC 4In/2Out Analog Block
;,m31>9[12],b09_OutMon, ; Ofs= 6 Len=12 IC670GBI001 Genius Bus Interface Unit
;,m31>22[2],b22_OutMon, ; Ofs= 18 Len= 2 IC660BBD024 12/24VDC 32 Ckt Source I/O Block
;The following lines map Diagnostics into ClxSlot 15
ClxSlot,15
DataInput ; Inputs to ControlLogix
0,BlockFlt, ; Ofs= 0 Len=2
2, ConnDiag
10,DiagCtrs, ; Ofs= 10 Len=10
;ControlLogix Connection Statistics
,ConnStats0, ; Ofs= 20 Len=10
Viewing the Current Configuration
To view the ControlLogix configuration currently stored in the AN-X, start the web
interface and select
View Active Configuration
.
Click the
Ethernet/IP
link to view the current ControlLogix scheduled data configuration.
AN-X2-GENI ControlLogix Config File /home/axctrl/GeniEnetIpSvr.csv
5: ;DisOutOnProg
7: ClxName: AnxGeniMas
8: ClxPrefix: GENI_
9: ClxSlot 0
11: DataOutput
12: 0 1 b01 b01_Out 16-Ckt Normally-open Relay Block
13: 1 1 b02 b02_Out 24/48VDC 16 Ckt Source I/O Block
14: 2 2 b03 b03_Out 24/48VDC 4In/2Out Analog Block
15: 4 12 b09 b09_Out Genius Bus Interface Unit
16: 16 2 b22 b22_Out 12/24VDC 32 Ckt Source I/O Block
21: DataInput