AN-X2-GENI (AN-X-GENI/B) Page
29
Example Configuration File
Example Configuration File:
;QTS AN-X2-GENI Scan Configuration Utility
;Copyright (c) 2005 Quest Technical Solutions
;Auto Config Ethernet/IP File
;ScanGeniProg
ClxName,AnxGeniMas
ClxPrefix,GENI_
ClxSlot,0
DataOutput ; Outputs from ControlLogix
,b1,b01_Out, ; Ofs= 0 Len= 1 IC660BBR101 16-Ckt Normally-open Relay Block
,b2,b02_Out, ; Ofs= 1 Len= 1 IC660BBD020 24/48VDC 16 Ckt Source I/O Block
,b3,b03_Out, ; Ofs= 2 Len= 2 IC660BBA020 24/48VDC 4In/2Out Analog Block
,b9,b09_Out, ; Ofs= 4 Len=12 IC670GBI001 Genius Bus Interface Unit
,b22,b22_Out, ; Ofs= 16 Len= 2 IC660BBD024 12/24VDC 32 Ckt Source I/O Block
,GlobSend; Global Data Sent by AN-X2-GENI
DataInput ; Inputs to ControlLogix
,BlockErr ; Map BlockErr here since Clx sets to -0xffffffff on Connection Failure
,b1,b01_Inp, ; Ofs= 2 Len= 1 IC660BBR101 16-Ckt Normally-open Relay Block
,b2,b02_Inp, ; Ofs= 3 Len= 1 IC660BBD020 24/48VDC 16 Ckt Source I/O Block
,b3,b03_Inp, ; Ofs= 4 Len= 4 IC660BBA020 24/48VDC 4In/2Out Analog Block
,b9,b09_Inp, ; Ofs= 8 Len=12 IC670GBI001 Genius Bus Interface Unit
,b16,b16_Inp, ; Ofs= 20 Len=32 IC693BEM331 Series 90-30 Bus Controller
,b22,b22_Inp, ; Ofs= 52 Len= 2 IC660BBD024 12/24VDC 32 Ckt Source I/O Block
,b31,b31_Inp, ; Ofs= 54 Len=32 IC697BEM731 Series 90-70 Bus Controller
;The following map 'Ghost Mode' Monitored Outputs to ClxSlot 8
;They must be 'uncommented' for 'Ghost Mode' Monitoring
;ClxSlot,8 ; This maps monitored 'Ghost Mode' outputs to Slot 8
;DataInput ; Inputs to ControlLogix