AN-X2-GENI (AN-X-GENI/B) Page
19
The part number for a module is defined by the keyword Part= and can be from 1 to 15
characters long. The part number text must be enclosed in double quotes, for example
Part="IC660BBD024".
The description for a module is defined by the keyword Desc= and can be from 1 to 95
characters long. The description text must be enclosed in double quotes, for example
Desc="12/24VDC 32 Ckt Source I/O Block".
The part number and description are used for comments only. You can put whatever you
want in them.
Each definition ends with the keyword EndBlock, which is required.
Parameter
Keyword
Valid entries
Serial bus address
Block=
0-31
Input length, bytes
Inp=
0-128
Output length, bytes
Out=
0-128
Scan mode
Scan
Scan
Part number
Part=
Maximum 15 characters, enclosed in
double quotes
Description
Desc=
Maximum 95 characters, enclosed in
double quotes
End of block definition
EndBlock
Examples:
Block=0,Inp=0,Out=0,,Part="IC660HHM501",Desc="Hand-held Monitor",EndBlock
Block=1,Inp=2,Out=2,Scan,Part="IC660BBR101",Desc="16-Ckt Normally-open Relay Block",EndBlock
When AN-X creates a Genius I/O configuration file after an autoconfiguration, it inserts
part numbers and descriptions from its internal module database.
Global Data Sent by AN-X2-GENI
If the AN-X2-GENI is to send global data on the Genius network, add a line of the form
GlobSend=length
to the configuration file. The length can be from 1 to 64. The length of global data is in
16-bit words, not bytes.