AN-X2-GENI (AN-X-GENI/B) Page
31
22: 0 2 BlockErr
23: 2 1 b01 b01_Inp 16-Ckt Normally-open Relay Block
24: 3 1 b02 b02_Inp 24/48VDC 16 Ckt Source I/O Block
25: 4 4 b03 b03_Inp 24/48VDC 4In/2Out Analog Block
26: 8 12 b09 b09_Inp Genius Bus Interface Unit
27: 20 8 b16 b16_Inp Series 90-30 Bus Controller
28: 28 2 b22 b22_Inp 12/24VDC 32 Ckt Source I/O Block
29: 30 64 b31 b31_Inp Series 90-70 Bus Controller
48: ClxSlot 15
50: DataInput
51: 0 2 BlockFlt
52: 10 10 DiagCtrs
55: 20 10 ConnStats0
......Parse Successful
Each line begins with a line number, from the original ControlLogix configuration file.
Each mapping line shows the offset and length of the data in the ControlLogix data
connection.
Saving the Current Configuration
To save the ControlLogix configuration currently stored in the AN-X to a file, start the
web interface and select
Automation Network/View Active Configuration
.
Right click the
Ethernet/IP
link and select
Save target
to save the current ControlLogix
scheduled data configuration to a file.
You can also save the ControlLogix configuration by selecting
Automation Network/View
Configuration Files
. Right click on the AN-X2-GENI ControlLogix Configuration File
link and select
Save target
to save the current ControlLogix scheduled data configuration
to a file.
Configuring the AN-X Module in RSLogix 5000
To configure the AN-X2-GENI in RSLogix 5000:
1.
Right click on the ControlLogix Ethernet module that will be communicating to the
AN-X and select
Add Module
. Add a 1756-ENBT/A module.
2.
Set the Major Rev to 1.