Page
40
AN-X2-GENI (AN-X-GENI/B)
May 2013
The contents of the right pane depend on the current command being executed.
TIP
Browsers may return cached data rather than rereading data that has
changed on the AN-X.
Run the browser in a mode where it doesn't cache data (incognito in
Chrome, Private browsing in Firefox and Safari, etc.)
Automation Network
Baud Rate and Serial Bus Address
Select
Automation Network/Genius Baud/Node Settings
to set the Genius network baud
rate and the serial bus address of the AN-X2-GENI.
To select the baud rate, check the radio button for the desired baud rate, either 38.4 Kbps,
76.8 Kbps, 153.6 Kbps Standard or 153.6 Kbps extended.
Enter the serial bus address (SBA) for the AN-X2-GENI, from 1 to 31.
Click the SUBMIT button to send the values to the AN-X.
Genius Network
Select
Automation Network/Genius I/O Network Configuration
to configure the I/O the
AN-X2-GENI is to scan.