TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Page 30 of 30
PV7069-T 01/05/16
Part number 129209
0.5
ALARM 2 (Lockout, stops heating) Input 2, Flash AL2 &
Lguage & valve= 2048 or 0x1000
bit # 11 or 12th bit
Pr2
0xD00
3329
0.5
ALARM 3 (Lockout, stops heating) Input
3/ALMMB/ALOAF, beep, Flash AL3 & Hguage & valve
(This is ALARM ON ANY FAILURE)= 4096 or 0x0800
bit # 12 or 13th bit
Pr2
0xD00
3329
0.5
Maintenance Relay1, beep, Flash Nn1 &
wrench=8192 or 0x2000 You must reset hours ou1 or
set oP1=0
bit # 13 or 14th bit
Pr2
0xD00
3329
0.5
Maintenance Relay2, beep, Flash Nn2 &
wrench=16384 or 0x4000 You must reset hours ou2
or set oP2=0
bit # 14 or 15th bit
Pr2
0xD00
3329
0.5
Maintenance Relay3, beep, Flash Nn3 &
wrench=32768 or 0x8000 You must reset hours ou3
or set oP3=0
bit # 15 or 16th bit
Pr2
0xD00
3329
0.3 & 0.5
On/Off On=257 or 0x0101, Off=1 or 0x0001 Can be
used to reset ALMMB alarm by cycling OFF, wait 30
sec , ON
Low byte is mask, Hi byte
is command. Bit # 0 & #8
Pr2
0x500
1281
0.3 & 0.5
Keyboard Lock Lock=2056 or 0x0808, Unlock=8 or
0x0008. If locked PoF is displayed when keypad edit is
attempted
Low byte is mask, Hi byte
is command. Bit # 3 &
#11
Pr2
0x500
1281
0.3 & 0.5
Reset audible alarm when condition is corrected,
4112 or 0x1010 does not reset alarm, just stops the
beeping
Low byte is mask, Hi byte
is command. Bit # 3 &
#12
Pr2
0x500
1281
Energy Savings Registers are enumerated 0 to 145
w/145=n/u
10 min each with 145=nu
All other enumerations start at 0 and count up