TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 10 of 30
PV7069-T 03/17
Part number 129209
CONFIRM OPERATION:
Heater Communication:
Communication between gateway and heaters is evident by rapid flashing of the TX and RX LEDs on the
gateway. If only the TX is flashing (may be as slow as 30 seconds between flashes), that will indicate no
response from the heaters.
Building Automation System Communication:
Using the HTML interface, you can confirm some operations and under USER MESSAGES, confirm there
are no errors messages. At this point, the BAS will need to discover the gateway and implement the points
into its integration.
TROUBLESHOOTING GATEWAY:
ERR Red LED on
o
Gateway is reporting an error.
o
Connect to gateway with HTML interface to view error messages
PWR LED not on
o
Confirm power on +PWR and
–PWR
TX & RX not flashing
o
Confirm connections to heaters and MODBUS addressing
o
Confirm gateway has been configured
TX flashing, RX not flashing
o
Gateway is talking to TempTrac, but not getting response from TempTrac. Confirm wiring,
confirm TempTrac is configured to proper address, Baud, Parity, Stop bits.
Verify polarity of all connections:
Set a Digital Volt Meter to read DC Volts. (Capable of reading less than 1.0VDC)
Pos. (red)
Probe
Neg. (black)
Probe
Min
Max
Actual
Reading
Gateway 6 pin terminal block
+PWR
-PWR
+9.0VDC
+30VDC
Tx/+
Rx/-
+0.1VDC
+5.5VDC
Gateway 3 pin terminal block (BACNET MSTP only)
RS 485 +
RS 485 -
+0.1VDC
+5.5VDC
TempTrac orange dongle (Each heater)
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
(+)
(-)
+0.1VDC
+5.5VDC
For advance gateway troubleshooting, reference the gateway manual.