TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 20 of 30
PV7069-T 03/17
Part number 129209
ALL POINTS INCLUDING ADVANCE:
Probe 1 C
Read Only
Controlling Probe Degrees C
MODBUS
BACNET
Probe1_C
25790
Deg-C
LONWORKS
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in
LONWORKS or MODBUS.
Probe 2 C
Read Only
Probe 2 in degrees C
MODBUS
BACNET
Probe2_C
25990
Deg-C
LONWORKS
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in
LONWORKS or MODBUS.
Probe 3 C
Read Only
Probe 3 in degrees C
MODBUS
BACNET
Probe3_C
26190
Deg-C
LONWORKS
Special BACNET point that converts the Probe value to degrees C in the gateway. Not available in
LONWORKS or MODBUS.
Manual Modulation
Read/Write
Force modulation to a level
MODBUS
Holding Register
797
40798
BACNET
PS4
79800
LONWORKS
NvoPS4_#
NviPS4_#
Used to force a modulation rate. Typically used by service tech to make combustion adjustments at a particular
firing rate. Normal setting is 101 = Auto. This allows the heater to modulate ad the load requires. If you put a
value 0-100, it will force the heater to that firing rate when operating. 0=Low Fire, 100=High Fire
Use with caution. Advise allowing the heater do control its own modulation.
ALL
Read/Write
Minimum Temperature Alarm
MODBUS
Holding Register
814
40815
BACNET
ALL
81500
Deg-F
LONWORKS
nvoALL_#
nviALL_#
Deg_F
Minimum temperature for Probe 1. Alarm will be activated if Probe 1 falls below this temperature. See Alarm
points.
ALU
Read/Write
Flame Current for proof of flame
MODBUS
Holding Register
815
40816
BACNET
ALU
81600
Deg-F
LONWORKS
nvoALU_#
nviALU_#
Deg_F
Maximum temperature for Probe 1. Alarm will be activated if Probe 1 rises above this temperature. See Alarm
points.
Burner Runtime
Read/Write
Burner Runtime Hours 0-65535
MODBUS
Holding Register
848
40849
BACNET
BURNER_HOURS_ou1
84900
Hours
LONWORKS
nvoBrnHr_ou1_ #
nviBrnHr_ou1_#
Hours
NOTE: Number of hours the burner has been enabled. Once it reaches 9999. This can be written to, as a way
to reset it.