TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP, AND POINTS LIST
Page 29 of 30
PV7069-T 01/05/16
Part number 129209
Adr
0.3 & 0.5
Serial address
0÷247
Pr2
Pr2
0x359
858
Ptb
0.3 & 0.5
Parameter map code always = 1
readable only
Pr2
Pr2
0x35A
859
rEL
0.3 & 0.5
Software release 5 = V0.5, 3 = V0.3
readable only
Pr2
Pr2
0x35B
860
i1S
0.5
Analog output when Digital Input 1 is activated
4-20mA
Pr2
0x35C
861
i1t
0.5
Analog output at i1S extra time if Digital Input 1 is not
activated
0÷30 sec.
Pr2
0x35D
862
i1d
0.5
Digital Input 1 Alarm Delay
0÷255 min.
Pr2
0x35E
863
i1F
0.5
If Yes, Digital Input 1 will function as Alarm. Operating
only when trying to call for output 1 and Input 1 is
active, subject to i1d timer
No; Yes
Pr2
0x35F
864
i2F
0.5
Digital Input 2 will function only when Output 1 is
energized
No; Yes
Pr2
0x360
865
i3F
0.5
Digital Input 3 will function only when Output 1 is
energized, When Edi is selected, Output 1 will open
when digital input 3 is activated
No; Yes; Edi
Pr2
0x361
866
oS2
0.5
Output 2 function: either temp relay or alarm relay
Std; AL
Pr2
0x362
867
(TP1)
0.3 & 0.5
Probe 1 temperature
Degrees F/C
Pr2
0x100
257
0.3
Probe 1 Information/Status Normal=512 or 0x0200,
Fault=515 or 0x0203. Fault will, drop call for heat, buz,
Flash Yellow P1, light yellow valve/M
bit (0,1 on) probe failure
Pr2
0x101
258
(TP2)
0.3 & 0.5
Probe 2 temperature
Degrees F/C
Pr2
0x102
259
0.3
Probe 2 Information/Status Normal=512 or 0x0200,
Fault=515 or 0x0203. Fault will buz, Flash Red P2
bit (0,1 on) probe failure
Pr2
0x103
260
(TP3)
0.3 & 0.5
Probe 3 temperature
Degrees F/C
Pr2
0x104
261
0.3
Probe 3 Information/Status Normal=512 or 0x0200,
Fault=515 or 0x0203. Fault will buz, Flash Red P3
bit (0,1 on) probe failure
Pr2
0x105
262
0.5
Modulation rate output (4 to 20mA)
0÷100%
Pr2
0x106
263
0.3 & 0.5
Statas of Relay 1,2&3
bit 0,1,2
Pr2
0x801
2050
0.3
Input 3 Alarm, buz, ALMMB, Flashes HP= 4096 or
0x0800
bit # 12 or 13th bit
Pr2
0xD00
3329
0.3
Input 2 Alarm, buz, Flashes LP= 4096 or 0x0800
bit # 12 or 13th bit
Pr2
0xD00
3329
0.3
Input 2 & 3, buz, Flashed HP & LP= 4096 or 0X0800
bit # 12 or 13th bit
Pr2
0xD00
3329
0.5
Low Temperature Alarm, beep, Flash Yellow LA= 1 or
0x0001
bit # 0 or 1st bit
Pr2
0xD00
3329
0.5
High Temperature Alarm, beep, Flash yellow HA= 2 or
0x0002
bit # 1 or 2nd bit
Pr2
0xD00
3329
0.5
Probe 1 error, open or shorted, Drops call for heat, yel
valve/M on, Flash Yellow P1=4 or 0x0004
bit # 2 or 3rd bit
Pr2
0xD00
3329
0.5
Probe 2 error, open or shorted, Flashing red P2=256
or 0x0100
bit # 8 or 9th bit
Pr2
0xD00
3329
0.5
Probe 3 error, open or shorted, Flashing red P3=512
or 0x0200
bit # 9 or 10th bit
Pr2
0xD00
3329
0.5
ALARM 1 (stops heating) Input 1, beep, Flash AL1 =
1024 or 0x0400. Will recover if Input 1 goes away, or
need for call for heat goes away
bit # 10 or 11th bit
Pr2
0xD00
3329