TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 21 of 30
PV7069-T 03/17
Part number 129209
ALL POINTS INCLUDING ADVANCE:
Maintenance Reminder
Read/Write
Number of burner cycles 0-9999
MODBUS
Holding Register
851
40852
BACNET
oP1
85200
LONWORKS
nvooP1_#
nvioP1_#
Maintenance feature, set the value to 0.
Output #2 Mode
Read/Write
Output #2 mode, ON, OFF, AUTO
MODBUS
Holding Register
855
40856
BACNET
TT_2on
85600
LONWORKS
nvoTT_2on_ #
nviTT_2on_#
TempTrac relay output spade 6 & 7. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat
functions).
Output #3 Mode
Read/Write
Output #2 mode, ON, OFF, AUTO
MODBUS
Holding Register
856
40857
BACNET
TT_3on
85700
LONWORKS
nvoTT_3on_#
nviTT_3on_#
TempTrac relay output spade 8 & 9. 0= Force relay off, 1=Force relay ON, 2= Auto (operates from thermostat
functions).
Software Version
Read Only
Firmware revision
MODBUS
Holding Register
859
40860
BACNET
VERSION_rEL
86000
LONWORKS
nvoVer_rEL_#
Software/Firmware revision number. At time of this manual, current version is 0.5 read as 5.
Modulation Rate
Read Only
Monitor the modulation signal
MODBUS
Holding Register
262
40263
BACNET
Modulation_FR
26300
LONWORKS
nvoMod_FR_#
Modulation rate on the analog output 4-20ma is represented as 0-100. This feature was introduced in Firmware
0.5 (5) and is not available from older TempTrac modules already in the field.
RELAYS Status ALL
Read Only
Shows the current state of the 3 output relays
MODBUS
Holding Register
2049
42050:0,1,2
BACNET
RELAYS
205000
LONWORKS
nvoRELAYS_#
This register contains the relay status for all 3 relays. Bit 0 = relay 1 (4&5), Bit 1 = relay 2 (6&7), Bit 2 = relay 3
(8&9). See below breakout of each relay.
Burner_Relay1
Read Only
Status of burner, Relay1 (Output 1)
MODBUS
Holding Register
2049
42050:0
BACNET
Burner_Relay1
205050
LONWORKS
nvoBrn_Rel1_#
This is Bit 0 of the Relay status word. It is the relay that controls the main heating output. Typically the Burner
Status. BACNET and LONWORKS have this broke out into state logic points. MODBUS, you will have to break
it out yourself. Read value, BITWISE AND with 0x0001, if result = 0, relay is off. If result = 1, relay is on.