TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 23 of 30
PV7069-T 03/17
Part number 129209
ALL POINTS INCLUDING ADVANCE:
Alarm_P2
Read Only
Status of Probe 1 Alarm
MODBUS
Holding Register
3328
43329:8
BACNET
Alarm_P2
332958
LONWORKS
nvoAlarm_P2_#
Probe 2 alarm. This can be a disconnected, open or shorted probe. This is Bit 8 of the ALARM STATUS ALL
word. Flashes ‘P2’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic
point.
For MODBUS ALARMS && 0x0100 = 0x0100 Alarm is active. = 0x0000 Alarm is not active.
Alarm_P3
Read Only
Status of Probe 1 Alarm
MODBUS
Holding Register
3328
43329:9
BACNET
Alarm_P3
332959
LONWORKS
nvoAlarm_P3_#
Probe 3 alarm. This can be a disconnected, open or shorted probe. This is Bit 9 of the ALARM STATUS ALL
word. Flashes ‘P3’ on TempTrac display. In BACNET and LONWORKS, this is broken out into a state logic
point.
For MODBUS ALARMS && 0x0200 = 0x0200 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL1
Read Only
Status of digital input #1 Alarm
MODBUS
Holding Register
3328
43329:10
BACNET
Alarm_AL1
332960
LONWORKS
nvoAlarm_AL1_#
Digital Input #1 alarm. This is typically not implemented. Refer to product specific details for information on this
alarm. This is Bit 10 of the ALARM STATUS ALL word. Flashes ‘AL1’ on TempTrac display. In BACNET and
LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0400 = 0x0400 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL2
Read Only
Status of digital input #2 Alarm
MODBUS
Holding Register
3328
43329:11
BACNET
Alarm_AL2
332961
LONWORKS
nvoAlarm_AL2_#
Digital Input #2 alarm. On some products, this is a general failure to operate alarm. See product specific
information. This is Bit 11 of the ALARM STATUS ALL word. Flashes ‘AL2’ or ‘LP’ on TempTrac display. In
BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x0800 = 0x0800 Alarm is active. = 0x0000 Alarm is not active.
Alarm_AL3
Read Only
Status of digital input #3 Alarm
MODBUS
Holding Register
3328
43329:12
BACNET
Alarm_AL3
332962
LONWORKS
nvoAlarm_AL3_#
Digital Input #3 alarm. On some products, this is a general failure to operate alarm. See product specific
information. This is Bit 12 of the ALARM STATUS ALL word. Flashes ‘AL3’ or ‘HP’ on TempTrac display. In
BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x1000 = 0x1000 Alarm is active. = 0x0000 Alarm is not active.