TEMPTRAC INTERFACE GUIDE, GATEWAY SETUP AND POINTS LIST
Page 24 of 30
PV7069-T 03/17
Part number 129209
ALL POINTS INCLUDING ADVANCE:
Alarm_Nn1
Read Only
Maintenance Alarm for output #1
MODBUS
Holding Register
3328
43329:13
BACNET
Alarm_Nn1
332963
LONWORKS
nvoAlarm_Nn1_#
Maintenance Alarm. This is enabled when the time on ou1 is greater than the value in oP1. Flashes ‘Nn1’ on
TempTrac display. Bit #13 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x2000 = 0x2000 Alarm is active. = 0x0000 Alarm is not active.
Alarm_Nn2
Read Only
Maintenance Alarm for output #2
MODBUS
Holding Register
3328
43329:14
BACNET
Alarm_Nn2
332963
LONWORKS
nvoAlarm_Nn2_#
Maintenance Alarm. This is enabled when the time on ou2 is greater than the value in oP2. Flashes ‘Nn2’ on
TempTrac display. Bit #14 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x4000 = 0x4000 Alarm is active. = 0x0000 Alarm is not active.
Alarm_Nn3
Read Only
Maintenance Alarm for output #3
MODBUS
Holding Register
3328
43329:15
BACNET
Alarm_Nn3
332963
LONWORKS
nvoAlarm_Nn3_#
Maintenance Alarm. This is enabled when the time on ou3 is greater
than the value in oP3. Flashes ‘Nn3’ on
TempTrac display. Bit #15 of Alarms. In BACNET and LONWORKS, this is broken out into a state logic point.
For MODBUS ALARMS && 0x8000 = 0x8000 Alarm is active. = 0x0000 Alarm is not active.
Com Status
Read Only
Communication Status bit
MODBUS
Input Register
NA
NA
BACNET
Gateway_TT_Com_OK
200
LONWORKS
nvoGwyTTCmOK_#
NOTE: This point is not generated by the heater; it is generated internally by the gateway. It is a status of the
communication connection between the gateway and the heater. If active (GOOD), the gateway is talking to the
heater. If inactive (NOT_PRESENT) then the gateway does not have good communication with the heater. This
point may take up to 3 minutes to register properly after communication is established or interrupted. If this
value if reading NOT_PRESENT, then no all over values are suspect, as the device is not communicating.
Generally the Gateway will hold the last value received. The only way to ensure you have the current values
from the heater is to verify this point is ACTIVE as well.