8.4 Settings - I/O Settings
Analog inputs are used to digitize signals that represent various primary values. There are a variety of
settings that can condition these input signals. These settings are briefly described below.
Parameter
Description
Range
Scale
Scaling factor, from secondary to primary values (ratio).
0..2 000
Decimals
Number of decimals for the value presented in the web interface.
0..3
Specialist settings
Settings
–
I/O Settings
Signal
Description
Range
Factory
value
Unit
No of
decimals
Dx Ly Current
Ratio phase y, detector x
1..2 000
300
2
A
1
Other factory default settings for the number of decimals are according to the following table.
Signal
Description
Factory value
No of decimals
Unit temperature
See section 7.5.1
1
Dx LN Current
See section 7.5.2
2
Dx Max fault current
See section 7.5.2
0
Dx Max current
See section 7.5.2
1
Dx Avg current period
See section 7.5.2
1
Dx Fault phase
See section 7.5.2
0
1
Does not affect the amplitude of the input signal.
2
Ratio Primary/Secondary current. Also applies to display of other currents.
Parameter
Description
Range
Offset
Offset added to the secondary value before scaling it.
0.000..1.000
Ref value
The reference value represents 100% of the nominal primary value, and
is used for the calculation of deadbands. For phase currents the
reference value is linked to the Scale value.
0..2 000
Unit - prefix
1
E.g., m(illi), k(ilo or M(ega).
-, m, k, M
Unit - unit
SI unit of the primary signal
-, A, W, VA, Hz, degC