7.4 Binary outputs
– I/O-addressing – Binary Outputs
Settings for all binary outputs are available on the
Config
–
I/O-addressing
–
Binary Outputs
subtabs
.
On the
Output 1-8
tab all physical outputs are listed.
Detector m
contains binary outputs for the detector functions.
All binary outputs have the same parameter settings. Below is a general description.
For more information on each individual item, see the following chapters.
Parameter
Description
Range
Unit
Description
Brief descriptive name for the object.
-
-
Type
Type of object;
Single
or
Double
1
.
Single command,
Double command
-
Settings
– Blocked
The signal is blocked, i.e. no order or command is
executed.
Yes or No
-
Settings
– Direct Excute
The order is executed directly, ie no
select
is needed.
Yes or No
-
Pulse time [ms]
Number of milliseconds that the output signal should be
high.
0 … 65 535
ms
Address 8
Upper octet of the address. Decimal.
0 … 255
-
Address 16
Lower octets of the address. Decimal.
0 … 65 535
-
1
For Double command <OFF> this means that output relay
n
is closed and output relay
n
+1 is opened. The command
<ON> opens output relay
n
and closes output relay
n
+1.