7.4.1 Binary Outputs
– Output 1-8/13/22
1
Settings for binary objects connected to physical outputs on the device, as well as the ACN button.
Only specific settings and differences to the normal are described below. See the beginning of this chapter
for a general description of the various configuration options.
From factory, all objects are set as
single command
and the sequence
selected / executed
.
The objects have the following factory settings:
▪
Type
-
Single command
▪
Settings - Blocked
- No
▪
Settings -
Negative
- No
▪
Pulse time
- 100 ms (200 ms fixed pulse time for object Ack)
Settings
–
Output 1-8/13/22
:
Parameter
Description
Factory value
address lower octets
2
Ack
Object connected to the ACN button on the front panel.
Can only have the type
single command
.
Pulse time cannot be changed, fixed time of 100 ms.
21000
Output n
Objects connected to physical outputs
n
.
21000+
n
Output 8
Object connected to physical output 8.
Can only have the type
single command
.
21008
Output 8 + n
Objects connected to physical outputs 8 +
n
(
n
= 1-4).
21008+
n
Output 13
Object connected to physical output 13.
Can only have the type
single command
.
21013
Output 13 + n
Objects connected to physical outputs 13 +
n
(
n
= 1-8).
21013+
n
Output 22
Object connected to physical output 22.
Can only have the type
single command
.
21022
1
If the device is an IPC4020exp4 or IPC4020exp6, there are additional physical binary outputs available.
2
The upper octet has always factory setting 0.