7.5.1 Analog Inputs
– Internal
Settings for internal analog objects of the device.
Only specific settings and differences to the normal are described below. See the previous page for a
general description of the configuration options.
Settings
–
Internal
:
Parameter
Description
Factory value
address lower octets
Unit temperature
Temperature measurement inside the device.
Default:
-
Type: Float [SI]
-
Blocked: No
-
Time tagged: No
-
Cyclic: No
-
Deadband: 5.0 %
3001
Type and Deadband
–
Internal
:
Object
Type / Deadband
Description
Unit temperature
Normalized [0-100 %]
Normalized to 100 degrees Celsius.
Normalized [0-120 %]
Normalized to 120 degrees Celsius.
Float [SI]
Floating point corresponding to Celsius degrees.
Scaled [SI*1]
Integers corresponding to Celsius degrees.
Scaled [SI*10]
Integers corresponding to 0.1 Celsius degrees
Scaled [SI*100]
Integers corresponding to 0.01 Celsius degrees.
Unit temperature
Deadband [%]
Set as a percentage of 100 degrees Celsius.