4.0. Digital Inputs and Outputs:
4.1 Digital Outputs
No of Digital Out Puts
8
Programmable Output
5
Annunciation 1
Annunciation 2
Annunciation 3
Annunciation 4
User Contact
User Contact could be assigned to any one of these functions
None
Unit Healthy
Heater/Choke.
Fuel Pump
Fixed Outputs
Crank
Fuel Solenoid (configurable as pull to start or pull to stop)
Hooter
4.2 Digital Inputs
There are eight digital inputs and each one of them can be assigned to perform a task as indicated
in the list below:
Assignable Functions
Descriptions
RWL
Radiator Water Level switch to trigger a fault in case of low coolant
Oil Level
Oil Level switch to shut down the engine on low oil level
Oil Temperature
Oil Temperature switch to shut down the engine on high Oil Temp.
Emergency
Emergency Stop signal
HET/HWT
High engine/coolant temperature switch. Though the unit has
provision for a temperature sensor. This input could be used to provide
additional protection.
Fuel
Low fuel level switch. Additional protection along with the fuel sensor
LLOP: Low Lube Oil
Pressure
Low LLOP switch. Additional protection along with Pressure sensor
R. Start/Stop
If assigned this function to a digital input the input could be used to
start/stop the genset in manual mode.
Connection to ground
: Start the Engine
Open
: Stop the Engine
Note
: Front Start/stop keys shall not work with this assignment.
R. Stop
Remote stop: If assigned this function to a digital input, the Digital
input shall, in manual mode, stop the engine, when connected to
ground. This could just be pulse of around 100ms
R. Start
Remote start: If assigned this function to a digital input, the Digital
input shall, in manual mode, start the engine, when connected to