13.0. In built Parameter:
The following tables give the detailed descriptions. Please note that 20sec of inactivity will take the
unit back in normal mode and all the changes done shall be discarded.
13.1 System Parameter
Parameter
Name on LCD
& Icon
Explanation of Parameter
Factory Setting
Setting Range
CAN J1939
CAN Bus enable/disable.
DGC1010 can be used engine
with CAN bus or without this bus.
Disabled
Disabled*
Enabled
Solenoid Type
Pull to Start
Cranking command occurs after
the solenoid pre time set in
generator parameter.
Fuel solenoid is kept pull till the
time engine is running. To stop
engine it is released.
Pull to Stop
Fuel solenoid is pulled to stop
the engine for a pre-programmed
duration.
Pull to stop
Pull to Stop
Pull to Start
LLOP Sensor
Type
Select the installed sensor for
LLOP.
There are many built in sensors
to choose from. For sensors
whose data is not in-built User
defined can be selected and the
sensor data programmed. Below
twenty parameters are for
programming the User defined
sensors. If a in-built sensor is
selected the following twenty
parameter shall not be displayed
TYPE A
User Defined
Type A
M&M
MNEPL
VE
TMTL
HUAFANG
TATA
GC(VDO)
GC(MURPHY)
4-20 ma
Disabled *
4-20 Max
Range
Max. Range of 4-20 mA LLOP
Sensor.
40
2-40
LLOP
Sensor R1
R1 to R10 = Resistance Value
V1 to V10 = Corresponding
pressure value.
10
0-999
LLOP
0.0
0.0-10.0