S.No
Description
1
Next Key. The preceding section describes the functions associated with all keys.
2.
Reset Key.
3.
Back Key.
4.
Forward Key.
5.
Increment/Start Key.
6.
Decrement/Stop Key.
7.
The area below shall indicate the status of engine. If the engine is running, engine
running is displayed.
8.
Warning LED. Warning led will blink in case of warning.
9.
Fault LED. Fault led blinks on a fault that resulted in engine shutdown.
10.
The input is activated on connection of dc negative at terminal no. 19. On
activation, DGC 101X disable trip function on all the faults. When PD is enabled, √
symbol shows in the right corner of the display. When PD is disabled,
x
symbol
symbol shows in the right corner of the display.
11
Parameter Window. All measure Parameter shall be displayed here.
12.
Icon of the parameter being displayed here.
13.
This icon indicates that the parameter of engine is displayed on the screen.
8.2 Backlight
Any event such as a front Key is pressed, Fault or Warning shall set the backlight to 100%
brightness. After 120 sec of expiry of the event the brightness of the backlight shall be reduced to
the programmed level. The level can be programmed from 10%-100%. During the cranking,
backlight shall be switched off.
9.0 Icons
9.1 Fault Icons
ICON DESCRIPTION
NOTES
START FAILED
The engine has not fired after the programmed number of starts
attempts
STOP FAILED
The controller has detected a condition that indicates that the
engine is running when it has been instructed to stop.
ENGINE HIGH
TEMPERATURE(HWT)
The controller detects that the engine coolant temperature has
exceeded the high engine temperature setting level and the
Safety On timer has expired.
LOW LUBE OIL
PRESSURE(LLOP)
The controller detects that the engine oil pressure has fallen
below the low oil pressure p
rogrammed
level and the Safety On
timer has expired.
UNDER RPM
The engine speed has fallen below the programmed RPM alarm
set
Содержание DGC-1010
Страница 1: ...DGC 101X Rev 1 0 OPERATING INSTRUCTIONS DGC 101X ...
Страница 39: ...Vibration 5Hz 8Hz at 7 5mm 8Hz 500Hz 2g IP65 From front 16 0 Dimensions ...
Страница 40: ......