ground. This could just be pulse of around 100ms
Note: There are some restriction on the assignment of the function to the Digital Inputs
a)
R. Start/Stop can not be selected along with either of R.Stop or R.start
b)
R.Start and R.Stop both must be assigned. Assigning only one is not allowed
5.0. Analog Sensors in Details
Though four sensors one each for Oil Temperature, Water Temperature, Pressure and Fuel are
installed but at times systems have typical requirements. DGC101X is deigned to cater for all these
possible requirements and these can be programmed in System Configuration Settings:
Requirement
Description
Sensor/Sensors are not
installed
In such case the display shall not display the measured sensor value
and the protection shall not be activated on the sensor readings.
Sensor/Sensors Installed but
not to protect the engine
If system requires to have the engine protected only through the
digital Input but the sensor measured values have to be displayed.
Sensor/Sensors installed and
used for Protection
Normal Operation
Fault in Sensors
The following faults in sensors are detected and announced:
Sensor Common Open.
Sensor Open
If Sensor Common Open is detected, non sensors shall be effective
If a Sensor Open on an individual sensor is detected, it renders that
sensor ineffective
6.0. Records
Fault Records
Last 64 Faults with time stamping. This is a circular buffer with last 64
faults. Newer fault shall replace the oldest fault(64). These can be
viewed on the LCD display or downloaded either by USB or RS485.
The faults logged are as per the list in 3.3(Supervision)
Event Records
Last 64 Events with time stamping. This is a circular buffer with last 64
Events. Newer Event shall replace the oldest event(64
th
). These can be
viewed on the LCD display or downloaded either by USB or RS485.
The events are:
1.
Parameters Modified
2.
RTC time changes
3.
Password Changed