alternator fault
occurs.
Hooter ON Time Duration for which the hooter
shall be ON, if not externally
reset, while announcing a fault.
30
1-100 Sec
Crank ON Time Maximum crank time.
5.0
1.0-20.0 Sec
Crank Gap Time The delay between two
successive cranks.
5
1-200 Sec
Crank Attempts The maximum number of cranks
that shall be attempted to start
the Engine.
3
1-10
Solenoid ON
time
The time for which stop solenoid
will be kept active while stopping
the engine.
Please note that in case of PULL
to Start mode this time should
be reduced (recommended 5
sec).
22
1-100 Sec
Auto Scroll
Setting ON will enable Auto
Scroll of display. OFF: No scroll
and next parameter can be
viewed by pressing next switch.
Auto Scroll On
Auto Scroll On
Auto Scroll Off
B.Light Dim % Backlight brightness while there
is no event, such as Key pressed,
fault or warning.
In normal case the display
brightness shall reduce to this
level after 120 sec of no event.
50
0-100
LCD Contrast
For increasing or decreasing the
Display Contrast.
10
1-20
Battery UV
Warning
Min. permissible battery voltage,
below this the voltage is treated
unhealthy & warning is
generated.
Disabled
Disabled*
9.1-35.0V
Battery OV
Warning
Max. permissible battery
voltage, above this the voltage is
treated unhealthy & warning is
generated.
Disabled
9.0-34.9V
Disabled*