Statistics values box DBV:
Above the measuring series is accepted, below not.
Cover values above the calculated upper
boundary are not considered and shown as
bars with a yellow frame only (see on the right
side bars at cover values 17 mm, 18 mm and
19 mm).
Figure 16:
Statistics Views DBV-Evaluation
For more details of the DBV-Evaluation please refer to the Info sheet
“Statistics according to DBV-Evaluation” available as pdf-file on the Pro-
fometer Touchscreen under Information/Documents and in the download
section of www.proceq.com.
Single-Line View
PM-630
PM-650
The Single-Line View can be displayed if measurements have been
done and stored in the Single-Line, Multi-Line or Cross-Line Mode (not
from Area-Scan Mode). It shows the rebar positions in a cross section.
The rebars are shown to scale depending on the diameter set. To show
them as a circle zoom the horizontal and vertical axis to the same scale.
However, for measurements over a long distance, like in a tunnel the
scale of the horizontal axis will be much smaller and the rebars shown
as vertical bars.
Figure 17:
Single-Line View with cover curve
Figure 17 shows a Single-Line View with Metric Unit, Minimum Cover
(dotted horizontal line in red) and Cover Curve (dotted curve in yellow).
In case a diameter was measured its value is shown in blue above the
rebar in the unit set. In case the diameter was manually set it is shown
in orange.
Figure 18 shows a Single-Line with the Signal Strength Curve (dotted
curve in yellow) set. The vertical axis shows the signal strength; hence
the Minimum Cover line is not shown.