Hazardous Location Installations - For USA and Canada
General
The Industrial Personal Computer has been designed with the intention of meeting
the requirements of Class I, Division 2 hazardous location applications. Division 2
locations are those locations where ignitable concentrations of flammable
substances are normally confined, prevented by ventilation, or present in an
adjacent Class I, Division 1 location, but where an abnormal situation might result in
intermittent exposure to such ignitable concentrations.
While the Industrial Personal Computer is a non-incendive device under
ANSI/ISA 12.12.01 and CSA C22.2 N
213, it is not designed for, and should never
be used within a Division 1 (normally hazardous) location.
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D
hazardous locations or in non-hazardous locations. Before installing or using your
Industrial Personal Computer, confirm that the ANSI/ISA 12.12.01 or
CSA C22.2 N
213 certification appears on the product labeling
NOTE:
Some Industrial Personal Computer devices are not yet rated as suitable for
use in hazardous locations. Always use your product in conformance with the
product labeling and this manual.
DANGER
POTENTIAL FOR EXPLOSION
Do not use your Industrial Personal Computer in hazardous environments or
locations other than Class I, Division 2, Groups A, B, C, and D.
Always confirm that your Industrial Personal Computer is suitable for use in
hazardous locations by checking that the ANSI/ISA 12.12.01 or
CSA C22.2 N
213 certification appears on the product labeling.
Do not install any Pro-face or OEM components, equipment, or accessories
unless these have also been qualified as suitable for use in Class I, Division 2,
Groups A, B, C, and D locations.
In addition, confirm that any PCI controller cards have an adequate temperature
code (T-code), and are suitable for a surrounding air temperature range of
0 to 50
C (32 to 122
F).
Do not attempt to install, operate, modify, maintain, service, or otherwise alter
the Industrial Personal Computer except as permitted in this manual.
Unpermitted actions may impair the unit’s suitability for Class I, Division 2
operation.
Failure to follow these instructions will result in death or serious injury.
Содержание PS-4600 Series
Страница 1: ......
Страница 12: ...About the Book 12...
Страница 14: ...General Overview 14...
Страница 26: ...Important Information 26...
Страница 56: ...Implementation 56...
Страница 72: ...Industrial Personal Computer Connections 72...
Страница 78: ...Configuration of the BIOS 78 Platform Information The figure shows the Main submenu...
Страница 118: ...Hardware Modifications 118 The figure shows the dimensions of the UPS battery unit...
Страница 170: ...Hardware Modifications 170...
Страница 172: ...Installation 172...
Страница 192: ...192...
Страница 196: ...After sales service 196...