PL-5910 Series User Manual
9-4
(Interface Ciruit)
Connection Example
Cable
R
PC357
Dsub 25 pin connector
4.7k
Ω
SSTA06
DOUT(-) pin 7
Alarm Output(-) pin 9
Lamp Output(-) pin 21
DOUT(+) pin 8
Alarm ) pin 10
Lamp ) pin 22
+5V
DC12V to
DC24V
Load
*1
External Output Signal
The PL unit’s RAS interface connector uses the following output signals.
General Purpose Signal Output (DOUT)
This general purpose digital output signal provides system condition information to
external devices.
The System Monitor’s API-DLL are used by applications to control this signal.
Alarm Output (1 point)
Lamp Output (1 point)
The above mentioned general purpose digital output signals provide system condition
information to external devices.
The System Monitor utility can be used to enable or disable any of these output signals.
Also, when Alarm Output is enabled, the indicator is always lit orange.
For connection pin location details,
2.3.5 RAS Interface
• Be sure to operate the unit within its maximum load current. If
the maximum load current exceeds this range, a malfunction or
PL damage may occur.
• Design your electrical system by adding the load current and
voltage values to the terminal voltage. If load current value used
is large, a maximum voltage of 1.5V will exist between the terminals.
• When connecting an induction load, be sure to connect the
above drawing's protection diode(*1).
Rated Load Voltage
DC12V to DC24V
Maximum Load Current
100mA/point
Maximum Voltage Drop between Terminals
1.5V (at 100mA load current)
Isolation Method
Via photocoupler