AIR 40, AIR Breeze, AIR 30, AIR X MARINE and AIR SILENT-X are trademarks of Primus Wind Power 2013 Primus Wind Power Inc.
AIR Owner’s Manual
3-CMLT-2020-A
27
AIR can produce high amperages. Protect your turbine with fuses or circuit
breakers. Wire with an appropriate size “slow-blow” fuse or circuit break-
er between AIR and the batteries. If a stop switch is used, the fuse or cir-
cuit breaker should be placed between the switch and the batteries.
Recommended Sizes for Circuit Breakers or Slow-Blow Fuses are detailed
on Technical Specifications page.
Install in accordance with CEC and NEC.
Circuit Breakers are available from Primus Wind Power.
FUSES, CIRCUIT BREAKERS AND AMPMETER
BATTERIES
Deep cycle batteries are required. Types include: flooded lead acid,
absorbed glass mat (AGM), gel cell, NiCad and Lithium Ion batteries. See
simple Sizing Tips for guidelines on battery sizing.
Fig. 15 Ammeter (Amp Meter)
NOTE:
An optional ammeter (sometimes called an Amp Meter) is an excellent addition to any system. It allows you to monitor the instantaneous current
output of your turbine. IMPORTANT: Place it between your turbine and the battery on the positive lead.
NOTE:
Primus Wind Power Inc. offers a combination of the above in the “Wind Control Panel” (WCP), available in both analog and digital versions. These
products are designed with a compact surface mount panel and optional weather resistant enclosure. Th analog and digital control panels contain the stop
switch, circuit breaker and ammeter (Amp Meter). See Appendix C at the back of the owner’s manual for further details.
NOTE:
For more information see:
www.batterycouncil.org
IMPORTANT:
Never use “automotive” batteries or
any battery other than “deep-cycle” batteries!
Circuit Breaker Sizing Recommendations:
AIR Model
PWP Recommendation
AIR 40/AIR BREEZE 48V
5 AMP
AIR 40/AIR BREEZE 24V
10 AMP
AIR 40 / AIR BREEZE 12V
20 AMP
AIR 30 / AIR X MARINE AND SILENT X 48V
20 AMP
AIR 30 / AIR X MARINE AND SILENT X 24V
25 AMP
AIR 30 / AIR X MARINE AND SILENT X 12V
40 AMP