Chapter 5 Function parameter
42
Ch
ap
ter 5
266.
F8.09 Short to ground protection
0:Invalid
1: Valid
1
☆
267.
F8.10 Number of automatic fault reset
0 to 32767
0
☆
268.
F8.11
Fault DO action selection during
automatic fault reset
0: OFF
1: ON
0
☆
269.
F8.12 Automatic fault reset interval
0.1s to 100.0s
1.0s
☆
270.
F8.13 Over-speed detection value
0.0 to 50.0% (maximum
frequency)
20.0%
☆
271.
F8.14 Over-speed detection time
0.0 to 60.0s
1.0s
☆
272.
F8.15
Detection value for too large
speed deviation
0.0 to 50.0% (maximum
frequency)
20.0%
☆
273.
F8.16
Detection time for too large
speed deviation
0.0 to 60.0s
5.0s
☆
274.
F8.17
Fault protection action selection
1
Units digit: Motor overload
(Err.11)
0: Free stop
1: Stop at the selected mode
2: Continue to run
Tens digit: input phase loss
(Err.12) (same as units digit)
Hundred digit: output phase loss
(Err.13) (same as units digit)
Thousand digit: external fault
(Err.15) (same as units digit)
Ten thousands digit:
Communication
abnormal( Err.16)(same as units
digit)
00000
☆
275.
F8.18
Fault protection action selection
2
Units digit: Encoder
fault(Err.20)
0: Free stop
1:Switch to V/F and then stop at
the selected mode
2:Switch to V/F and continue to
run
Tens digit: function code read
and write abnormal (Err.21)
0: Free stop
1: Stop at the selected mode
Hundreds digit: Reserved
Thousands digit: Motor
overheating (Err.45) ( same as
F8.17 units digit)
Ten thousands digit: Running
time arrival(Err.26)(same as
F8.17 units digit)
00000
☆
276.
F8.19
Fault protection action selection
3
Units digit:User-defined fault
1(Err.27) (same as F8.17 units
00000
☆