Chapter 5 Function parameter
35
Ch
ap
ter 5
131.
F2.14 Relay 2 output delay time
0.0s to 3600.0s
0.0s
☆
132.
F2.15 DO output terminal active status selection
Units digit: SPB
switching quantity
0: positive logic
1: anti-logic
Tens digit: Relay 1
Hundreds digit:
Hundreds digit:
Undefined
Thousands digit: SPA
Ten thousands digit:
Relay 2
00000
☆
133.
F2.16 DA1 zero bias coefficient
-100.0% to +100.0%
0.0%
☆
134.
F2.17 DA1 gain
-10.00 to +10.00
1.00
☆
135.
F2.18 DA2 zero bias coefficient
-100.0% to +100.0%
0.00%
☆
136.
F2.19 DA2 gain
-10.00 to +10.00
1.00
☆
5-1-5.
F3 Group - Start and stop control group
No. Code
Parameter name
Setting range
Factory
setting
Chan
ge
137.
F3.00 Start-up mode
0: Direct startup
1: Speed tracking restart
2: Pre-excitation start (AC
asynchronous motor)
0
☆
138.
F3.01 Speed tracking mode
0~2: reserve
3: Rotate speed tracking method3
3
★
139.
F3.02 Speed tracking value
1 to 100
20
☆
140.
F3.03 Start frequency
0.00Hz to 10.00Hz
0.00Hz
☆
141.
F3.04 Hold time for start frequency
0.0s to 100.0s
0.0s
★
142.
F3.05 DC beforehand field current
0% to 100%
0%
★
143.
F3.06 DC excitation time beforehand 0.0s to 100.0s
0.0s
★
144.
F3.07 Stop mode
0: Deceleration parking 1: Free stop
0
☆
145.
F3.08 DC Initial frequency
0.00Hz to F0.19 (maximum
frequency)
0.00
Hz
☆
146.
F3.09 DC Waiting time
0.0s to 100.0s
0.0s
☆
147.
F3.10 Stop DC braking current
0% to 100%
0%
☆
148.
F3.11 Stop DC braking time
0.0s to 100.0s
0.0s
☆
149.
F3.12 Braking utilization rate
0% to 100%
100%
☆