16 Appendix
Precision Pulse Output Description
Introduction
The PowerMaster
®
incorporates a high accuracy pulse output which can be driven by any of the
following quantities:
Active Power (P):
Pa:
active power computed in the time domain ( once per cycle).
Includes DC and all frequency components up to 3 kHz.
P1:
active power computed in the frequency domain ( once every four
cycles). Includes only the fundamental frequency component.
Pt:
active power computed in the frequency domain ( once every four
cycles). Can include up to the 50
th
harmonic. The maximum
number of harmonics to include are user selectable. A threshold
(as a percent of the fundamental) can also be set to exclude
harmonics with very low amplitudes.
Reactive Power (P): Qa:
reactive power computed in the time domain ( once per cycle).
Includes DC and all frequency components up to 3 kHz.
Q1:
reactive power computed in the frequency domain ( once every four
cycles). Includes only the fundamental frequency component.
Qt:
reactive power computed in the frequency domain ( once every four
cycles). Can include up to the 50
th
harmonic. The maximum
number of harmonics to include are user selectable. A threshold
(as a percent of the fundamental) can also be set to exclude
harmonics with very low amplitudes.
Apparent Power (P): Sa:
reactive power computed in the time domain ( once per cycle).
Includes DC and all frequency components up to 3 kHz.
S1:
reactive power computed in the frequency domain ( once every four
cycles). Includes only the fundamental frequency component.
St:
reactive power computed in the frequency domain ( once every four
cycles). Can include up to the 50
th
harmonic. The maximum
number of harmonics to include are user selectable. A threshold
(as a percent of the fundamental) can also be set to exclude
harmonics with very low amplitudes.
Rev 1.5
155
Содержание PowerMaster 3 Series
Страница 1: ...PowerMaster 3 Series Firmware Version 2 0 0 10 Product Manual Revision 1 5 Rev 1 5 1...
Страница 57: ...Meter View Connection View Rev 1 5 57...
Страница 78: ...Rev 1 5 78...
Страница 96: ...11 2 1 CT Testing Results Graphs 11 2 1 1 CT Testing Results Data Description Rev 1 5 96...
Страница 154: ...302 305 and 335 accessories maintain IEC 61010 compliance only when connected to a complaint 3 Series Rev 1 5 154...