Symptom
Possible Cause
Solution
Three-phase units only:
Platform does not rise.
Motor hums, but does
not run.
No voltage is present on
one line.
NOTE: A motor that is
missing voltage on one line
is said to be single-phased.
Check for blown fuses at branch circuit disconnect.
Replace fuse. Determine cause of blown fuse.
Check motor starter as follows:
1. Disconnect wires at load side of starter.
2. Energize the starter.
3. Measure line-to-line voltage at line side of starter.
4. Measure line-to-line voltage at load side of
starter.
5. Line-side and load-side voltages should be
approximately the same. Replace starter if
voltage values are considerably different from
one another.
Check all wiring to motor for high resistance or no
connection.
Single-phase units only:
Platform does not rise.
Motor energizes, but
does not run.
Line voltage too low.
Check wiring to motor for high resistance. Check for
loose or corroded connections. Check if gauge of
wires to motor are of correct size and specification
for load requirement. Replace if necessary.
Faulty motor centrifugal
switch.
Replace motor.
Faulty motor capacitor.
Replace motor.
Platform does not
rise. Pump operates in
pressure relief mode.
Heavy object(s) on platform.
Remove object(s) from platform.
Note:
For safety reasons, the dock leveler is
designed to lift only the platform’s own weight.
Dock leveler binds.
Check for visible obstructions that could cause
binding. Remove obstructions. If no obstructions
found, contact Systems, LLC Technical Services.
Pressure relief set too low.
Increase pressure relief. See page 32 for instruction.
Note:
The pressure relief valve must not be set
at a level that causes the motor operating current
to exceed the full load amp value* at any time,
including when operating in pressure relief.
* The full load amp value can be found on the inside cover of the
control panel.
TROUBLESHOOTING
Содержание LHP Series
Страница 13: ...11 4111 0012 Sept 2018 2018 Systems LLC This page intentionally left blank INSTALLATION ...
Страница 25: ...23 4111 0012 Sept 2018 2018 Systems LLC INSTALLATION This page intentionally left blank ...
Страница 31: ...29 4111 0012 Sept 2018 2018 Systems LLC MAINTENANCE This page intentionally left blank ...
Страница 42: ...40 4111 0012 Sept 2018 2018 Systems LLC PARTS B A D C Lip and Platform Parts ...
Страница 47: ...45 4111 0012 Sept 2018 2018 Systems LLC PARTS This page intentionally left blank ...
Страница 49: ...47 4111 0012 Sept 2018 2018 Systems LLC PARTS This page intentionally left blank ...
Страница 50: ...48 4111 0012 Sept 2018 2018 Systems LLC This page intentionally left blank MISCELLANEOUS ...