Page
57
of
76
MICRO-0.25/0.3-I-OUTD-US-208-240
BCG.00612_AB
Part
5
Troubleshooting Guide
Once the short-circuit has been made, measure the insulation resistance (Riso) using a
megohmmeter positioned between the two shorted poles and ground (of the inverter).
If the measured insulation resistance is less than 1Kohm the inverter does not connect to the grid
due to a low insulation of photovoltaic module respect to ground.
The insulation resistance is affected by the environmental conditions the photovoltaic module
is in (E.g.: photovoltaic module wet from dump or rain); therefore, the measurement must be
made immediately after the anomaly.
Содержание AURORA MICRO-0.25-I-OUTD-US-208/240
Страница 1: ...THE MANUAL MICRO Model Number MICRO 0 25 I OUTD US 208 240 MICRO 0 3 I OUTD US 208 240...
Страница 2: ...AURORA MICRO Grid Tied Inverters MICRO 0 25 0 3 I OUTD US 208 240 Technical Manual...
Страница 31: ...Page 30 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 3 MOUNTING AND WIRING...
Страница 45: ...Page 44 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 4 OPERATIONS GUIDE...
Страница 51: ...Page 50 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 5 TROUBLESHOOTING...
Страница 60: ...Page 59 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 6 MAINTENANCE GUIDE...
Страница 64: ...Page 63 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 7 APPENDIX...
Страница 65: ...Page 64 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Part 7 Appendix 7 1 TECHNICAL DATA...
Страница 72: ...Page 71 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Part 7 Appendix Figure 7 9 Topographic Diagram...