Page
40
of
76
MICRO-0.25/0.3-I-OUTD-US-208/240
BCG.00612_AB
Part
3
Mounting and Wiring
3.3
WIRING DETAILS
3.3.1
L
OAD
P
ROTECTION
S
WITCH
(AC
DISCONNECT SWITCH
)
To protect each AC connection line of the MICRO inverter, it is required to install a device for
protection against overcurrent with the following characteristics:
Table 3-1: Overcurrent device recommended characteristics
Protection breaker
rating
6A
10A
16A
20A
Max number of
Inverters
@240VAC
MICRO-
0.25
4
7
12
15
MICRO-
0.3
3
6
9
12
Max number of
inverters
@208VAC
MICRO-
0.25
4
6
10
13
MICRO-
0.3
3
5
8
11
The dimensions of the thermal-magnetic circuit breaker should be determined by the number of
MICRO inverters connected to a single AC line. A 20A thermal-magnetic circuit breaker represents
the maximum value permitted for installation in a single AC line, sized based on the AC cable cross
section (10 AWG).
It is the installer’s responsibility to adequately size the overcurrent protection,
based on the number and types of MICRO inverters in the system (see
Table
3-1
). The maximum thermal-magnetic circuit breaker current rating is 20A for
each AC line.
Содержание AURORA MICRO-0.25-I-OUTD-US-208/240
Страница 1: ...THE MANUAL MICRO Model Number MICRO 0 25 I OUTD US 208 240 MICRO 0 3 I OUTD US 208 240...
Страница 2: ...AURORA MICRO Grid Tied Inverters MICRO 0 25 0 3 I OUTD US 208 240 Technical Manual...
Страница 31: ...Page 30 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 3 MOUNTING AND WIRING...
Страница 45: ...Page 44 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 4 OPERATIONS GUIDE...
Страница 51: ...Page 50 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 5 TROUBLESHOOTING...
Страница 60: ...Page 59 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 6 MAINTENANCE GUIDE...
Страница 64: ...Page 63 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 7 APPENDIX...
Страница 65: ...Page 64 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Part 7 Appendix 7 1 TECHNICAL DATA...
Страница 72: ...Page 71 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Part 7 Appendix Figure 7 9 Topographic Diagram...