MICRO-0.25/0.3-I-OUTD-US-208-240
BCG.00612_AB
Part
5
Troubleshooting Guide
Alarm
Messages
Code
displayed
Cause
Solution
Vbulk UV
W011
Internal fault of the booster circuit inverter
Contact Power-One Service.
Comm
warning
W025
The alarm is generated when the CDD
device does not receive messages from the
MICRO inverter for more than 5 minutes.
This may be caused by non-optimal
positioning of the CDD.
Consider a new installation position that
ensures better communication between the
CDD device and the MICRO inverters. Use
the CDD Internal Web Server to verify the
signal quality (refer to the CDD manual for
information on the Internal Web Server)
Comm
fault
W005
The alarm is generated when the CDD
device does not receive messages from the
MICRO inverter for more than 15 minutes.
This may be caused by non-optimal
positioning of the CDD.
Consider a new installation position that
ensures better communication between the
CDD device and the MICRO inverters. Use
the CDD Internal Web Server to verify the
signal quality (refer to the CDD manual for
information on the Internal Web Server)
Remote
Off
E035
The alarm is generated when an external
shutdown command has been sent to the
MICRO inverter.
Disable the Remote Off command.
Содержание AURORA MICRO-0.25-I-OUTD-US-208/240
Страница 1: ...THE MANUAL MICRO Model Number MICRO 0 25 I OUTD US 208 240 MICRO 0 3 I OUTD US 208 240...
Страница 2: ...AURORA MICRO Grid Tied Inverters MICRO 0 25 0 3 I OUTD US 208 240 Technical Manual...
Страница 31: ...Page 30 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 3 MOUNTING AND WIRING...
Страница 45: ...Page 44 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 4 OPERATIONS GUIDE...
Страница 51: ...Page 50 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 5 TROUBLESHOOTING...
Страница 60: ...Page 59 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 6 MAINTENANCE GUIDE...
Страница 64: ...Page 63 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Technical Manual PART 7 APPENDIX...
Страница 65: ...Page 64 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Part 7 Appendix 7 1 TECHNICAL DATA...
Страница 72: ...Page 71 of 76 MICRO 0 25 0 3 I OUTD US 208 240 BCG 00612_AB Part 7 Appendix Figure 7 9 Topographic Diagram...