Display
Name /
Description
Range
Function
Set on
RUN
2 CNTROL
MODE2=2
G4.1.2 /
Alternative
Control Mode
0-3
It allows user to set the control mode for the drive
commands (Start/Stop, Reset, ...).
OPT.
DESCRIPTION
FUNCTION
0
NONE
Ctrl mode 2 is not
operative
1
LOCAL
Drive controlled by
keypad.
2
REMOTE
Drive controlled through
control terminals.
3
SERIAL COMMS
Drive controlled through
communication bus.
Note
: Control mode 2 will be activated through digital
inputs exclusively. To use this set one of the digital
inputs to '17
CONTROL 2'. When this input is
activated, auxiliary control mode will be activated.
NO
3.3.2.
Subgroup 20.0
–
G20.0: Communications Control
This subgroup specifies the communication module to be used.
Once previous parameters are set, the subgroup [20.0] will specify
the particular communication bus to use.
Display
Name /
Description
Range
Function
Set
on
RUN
1 COM.
CONTROL=0
G 20.0.1 /
Communication
Module
0-5
Set the value according to communications network
controlling the drive
Note:
This parameter is only functional after the boot up.
OPT.
FUNCTION
0
Modbus
1
Profibus
2
Modbus TCP
3
Ethernet_IP
4
Can Open
5
Devicenet
SI
Содержание ProfiPower SD700 Type 1
Страница 1: ...Communication Network Profibus Communication...
Страница 2: ......
Страница 3: ...Communication Network Profibus Communication Edition April 2015 SD70BC03EI Rev E...
Страница 4: ...SD700 PROFIBUS POWER ELECTRONICS 2...
Страница 6: ...SD700 PROFIBUS POWER ELECTRONICS 4...
Страница 8: ...SD700 PROFIBUS POWER ELECTRONICS 6 INDEX...
Страница 14: ...SD700 PROFIBUS POWER ELECTRONICS 12 SAFETY INSTRUCTIONS...
Страница 45: ...www power electronics com...