POWER ELECTRONICS
SD700
–
PROFIBUS
TRIAL RUN
33
E
N
G
L
I
S
H
4.3.3.
Profipower SD700 Type 3 Module
This module and the next one are modules for the SD700 that
already have the Modbus registers for reading and writing defined.
User only must write the value of the registers.
Pre-defined registers for these modules are shown in the attached
table.
The Profibus board receives 10 bytes of output data of the Profibus-
DP Master.
Output
Data
(Word)
Param.
Modbus
Address
Variables
Range
Modbus Range
0
G3.3
40124 LOCAL_SPEED_REF
-250 to +250%
-20480 to + 20480
1
-
40562 HOST_START_CONTROL
0 to 1
0 to 1
2
-
40563 HOST_STOP_CONTROL
0 to 1
0 to 1
3
-
40564 HOST_RESET_CONTROL
0 to 1
0 to 1
4
-
40565 HOST_TRIP_CONTROL
0 to 1
0 to 1
The Profibus board sends 4 bytes of input data to the Profibus-DP
Master.
Output
Data
(Word)
Param.
Modbus
Address
Variables
Modbus Range
0
SV1.1
40162
ACTUAL_SPEED_REFERENCE 8192 = 100% of motor rated speed
1
STATUS
LINE
40219
GENERAL_STATUS
0 to 201