3-34
PFC-6075 • 5403593 • Rev C • 2/13
The
50 programmable LED outputs
are located on connectors
P1-P5
, each containing ten (10) LeD outputs and two (2) 5vDC
outputs. The
system LEDs
and
PZT control outputs
are located on connector
P6
. LeDs are wired as shown below; no external
resistor is required. All outputs are power limited.
DRV-50 "P1-P5" and "P6" Connectors
Figure 37.
The
4 programmable dry-contact inputs
are located on connector
P7
. All input circuits are power limited and use a 5.1k eOL
resistor. The inputs can be programmed for any of the contact input functions available for other input circuits available on the
panel.
DRV-50 "P7" Dry-Contact inputs
Figure 38.
The higher current required for the LeD outputs can be provided by the panel, or from an auxiliary power source as shown below.
The auxiliary power can be any 24vDC source, and is fully supervised.
Examples of Wiring DRV-50 from Control Panel or Auxiliary Power Supply
Figure 39.
TRB
SUP
ALR
SIL
EARTH
PWR
PZT-
LED+
LED1
LED10
LED+
LED+
Programmable LED
Connectors P1-P5
System LED and PZT
Connector P6
DWG #608-8
LED PWR P -Link
-
+ -
+ A B
P-Link from
control panel
Example:
Powered by
control panel
LED PWR P -Link
-
+ -
+ A B
P-Link from
control panel
Example:
Powered by
aux supply
Power from
auxiliary
supply
DWG #608-9B
Dry Contact Inputs (P7)
I1
I2
I
3
I
4
5.1k
5.1k
5.1k
5.1k
P7
DWG #608-9
Max. wiring resistance = 100 ohm
Max. wiring capacitance = 1 uF
Max. wiring length = 10,000 ft.
Max. IDC voltage = 24 vDC
Max. IDC current = 5 mA